| 2021-10-06 12:54:45 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21090703 |
| | 10/6/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P100: PROVIDE A SANITARY DRAINAGE AND VENT |
| | ISOMETRIC DRAWING- SECTION 107.3.5.3 WPB. |
| | |
| | 2) P100: PLEASE PROVIDE A PLUMBING SCOPE OF WORK |
| | NARRATIVE ON THE PLAN. INDICATE WHICH FIXTURES, |
| | APPLIANCES, FAUCETS ETC. ARE BEING REPLACED- SECTION |
| | 107.2.1 WPB. |
| | |
| | 3) P100: PROVIDE THE MAKE AND MODEL OF THE NEW WATER |
| | HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- TABLE |
| | C404.2 FBC EC AND SECTION P2801.1 FBC RES. |
| | |
| | 4) P100: PROVIDE HOT WATER PIPE SPECIFICATIONS- TABLE |
| | C403.2.10 FBC EC. |
| | |
| | 5) P100: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR |
| | THE STEAM EQUIPMENT AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS- SECTION 107.2.1 WPB. PROVIDE A PIPING |
| | DIAGRAM ON THE PLAN- SECTION 107.3.5.3 WPB. |
| | |
| | 6) FLOOD ZONE HAZARD: THE PROPERTY APPEARS TO BE IN AN |
| | AE FLOOD HAZARD ZONE. ACCORDING TO SECTION R322.1.6 FBC |
| | RES, PLUMBING FIXTURES, APPLIANCES, PIPING ETC. SHALL |
| | BE INSTALLED AT OR ABOVE THE ELEVATION REQUIRED IN |
| | SECTION R322.2 FBC RES. |
| | |
| | 7) PLEASE SHOW COMPLIANCE WITH R322.1.7 PROTECTION OF |
| | WATER SUPPLY AND SANITARY SEWAGE SYSTEMS NEW WATER |
| | SUPPLY AND SANITARY PIPING SYSTEMS. NEW AND REPLACEMENT |
| | WATER SUPPLY SYSTEMS SHALL BE DESIGNED TO MINIMIZE OR |
| | ELIMINATE INFILTRATION OF FLOOD WATERS INTO THE SYSTEMS |
| | IN ACCORDANCE WITH THE PLUMBING PROVISIONS OF THIS |
| | CODE. NEW AND REPLACEMENT SANITARY SEWAGE SYSTEMS SHALL |
| | BE DESIGNED TO MINIMIZE OR ELIMINATE INFILTRATION OF |
| | FLOODWATERS INTO SYSTEMS AND DISCHARGES FROM SYSTEMS |
| | INTO FLOODWATERS IN ACCORDANCE WITH THE PLUMBING |
| | PROVISIONS OF THIS CODE AND IN ACCORDANCE WITH CHAPTER |
| | 64E-6, FLORIDA ADMINISTRATIVE CODE, STANDARDS FOR |
| | ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEMS. SEE ALSO |
| | SECTION 7.3 ASCE 24-14. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |