| 2022-03-17 10:06:38 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21090688 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGY CALCULATIONS AND THE MECHANICAL EQUIPMENT |
| | SIZING CALCULATIONS ARE FOR A 2 STORY ADDITION FOR AN |
| | EXISTING HOUSE FOR A TOTAL OF 2992 SQUARE FOOT OF NEW |
| | SPACE. IN THE MECHANICAL EQUIPMENT SIZING CALCULATIONS, |
| | ZONE 1 IS FOR THE 1ST FLOOR ADDITION SQUARE FOOTAGE |
| | WHICH IS 1496. THE AHU 1 IS LOCATED IN THE GARAGE AND |
| | HAS DUCTWORK THROUGHOUT THE ENTIRE FIRST FLOOR WHICH |
| | INCLUDES THE EXISTING SQUARE FOOTAGE OF THE HOME. IF |
| | AHU-1 IS TO CONDITION BOTH THE EXISTING SQUARE FOOTAGE |
| | AND THE NEW SQUARE FOOTAGE OF THE 1ST FLOOR YOU MUST |
| | PROVIDE A MECHANICAL EQUIPMENT SIZING CALCULATION FOR |
| | THE ENTIRE 1ST FLOOR AREA AND SIZE AHU-1 ACCORDINGLY. |
| | IT DOES NOT APPEAR THAT AHU-1 COULD BE SIZED THE SAME |
| | AS AHU-2 AS AHU-1 SERVES A LARGER SQUARE FOOTAGE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |