| Plan Review Notes For Permit 21090681 |
| Permit Number |
21090681 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-20 15:13:59 | 1ST REVIEW FBC-2020 RES. | | | PERMIT- 21090681 | | | 10/20/21 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET MP-1G: NON-COMPLIANT WET VENTS FOR THE | | | BATHROOMS. A) NOT MORE THAN ONE WET-VENTED FIXTURE | | | DRAIN (WC, SHOWER) SHALL DISCHARGE UPSTREAM OF THE DRY | | | VENT FOR THE LAV- SECTION P3108.2.1 FBC P. B) THE | | | FIXTURE DRAIN FOR THE BAR SINK SHALL NOT CONNECT TO THE | | | WET VENT FOR THE GARAGE BATHROOM- SECTION P3108.1 FBC | | | RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|