| 2021-09-27 08:23:29 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 21090630 | | | 9/27/21 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) INDICATE THE TYPE OF GAS SUPPLY TO THE GRILL AND | | | SHOW THE SOURCE OF THE GAS- SEE PAGES 26 AND 27 OF THE | | | SUBMITTED MANUAL- SECTION 107.2.1 WPB. NATURAL GAS | | | INSTALLATION WILL REQUIRE SUBMITTAL OF A GAS RISER | | | DRAWING- SECTION G2413.1 FBC RES. | | | | | | 2) REFER TO PAGE 24 OF THE MANUAL AND SHOW THE | | | LOCATIONS AND SIZES OF REQUIRED VENTILATION OPENINGS | | | FOR THE BUILT-IN GRILL- G2447.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|