Plan Review Notes
Plan Review Notes For Permit 21090630
Permit Number 21090630
Review Stop G
Sequence Number 1
Notes
Date Text
2021-09-27 08:23:291ST REVIEW FBC-2020 RES. GAS
 PERMIT- 21090630
 9/27/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) INDICATE THE TYPE OF GAS SUPPLY TO THE GRILL AND
 SHOW THE SOURCE OF THE GAS- SEE PAGES 26 AND 27 OF THE
 SUBMITTED MANUAL- SECTION 107.2.1 WPB. NATURAL GAS
 INSTALLATION WILL REQUIRE SUBMITTAL OF A GAS RISER
 DRAWING- SECTION G2413.1 FBC RES.
  
 2) REFER TO PAGE 24 OF THE MANUAL AND SHOW THE
 LOCATIONS AND SIZES OF REQUIRED VENTILATION OPENINGS
 FOR THE BUILT-IN GRILL- G2447.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  