Plan Review Notes
Plan Review Notes For Permit 21090600
Permit Number 21090600
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-20 13:07:1509/20/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLUMBING ISOMETRIC FOR MASTER BATH DOES NOT MATCH
 THE LAYOUT, PLEASE SHOW THE BATHROOM GROUP ON ITS
 SYSTEM AND NOT IN THE TRUNK LINE DISCHARGE AND PLEAS
 SIZE THE DISCHARGE FOR THE WASHING MACHINE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 PLUMBING.
  
 2. THE WASHING MACHINE SHUT-OFF VALVES SHALL BE
 ACCESSIBLE WITHOUT MOVING THE UNITS AND WITHIN REACH
 PER THE 2017 FBC SEC. R 2903.9.3.
  
 3. ON-HOUSE PLAN SHOWING THE LOCATION OF THE TANK-LESS
 WATER HEATER SHOWS THE LOCATION AND DISTANCE OF ANY
 OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE SITE OF THE WATER HEATER SHALL COMPLY WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3.
  
 5. VALVE UNDER LAV SHALL HAVE SHUT OFF IN AN ACCESSIBLE
 LOCATION, VALVES SERVING INDIVIDUAL PLUMBING FIXTURES,
 PLUMBING APPLIANCES, RISERS, AND BRANCHES SHALL BE
 ACCESSIBLE PER THE 2020 P2903.9.3 FIXTURE VALVES AND
 ACCESS.
  
 6. THE SHOWER VALVES SHALL BE EQUIPPED WITH CONTROL
 VALVES OF THE PRESSURE-BALANCE, THERMOSTATIC-MIXING, OR
 COMBINATION PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE
 TYPES WITH A HIGH LIMIT STOP IN ACCORDANCE WITH ASSE
 1016/ASME A112.1016/CSA B125.16. THE HIGH LIMIT STOP
 SHALL BE SET TO LIMIT THE WATER TEMPERATURE TO EXCEED
 120 F. IN-LINE THERMOSTATIC VALVES SHALL NOT BE USED TO
 COMPLY WITH THIS SECTION PER THE 2020 FBC R 2708.4
 SHOWER CONTROL VALVES.
  
 7. THE HAND-HELD SHOWERS SHALL CONFORM TO ASME
 A112.18.1/CSA B125.1. HAND-HELD SHOWERS SHALL PROVIDE
 BACKFLOW PROTECTION IN ACCORDANCE WITH ASME
 A112.18.1/CSA B125.1 OR SHALL BE PROTECTED AGAINST
 BACKFLOW BY A DEVICE COMPLYING WITH ASME A112.18.3 PER
 THE 2020 FBC R 2708.5 HAND SHOWERS.
  
 8. THE WASHING MACHINE SHUT-OFF VALVES SHALL BE
 ACCESSIBLE WITHOUT MOVING THE UNITS AND WITHIN REACH
 PER THE 2020 FBC SEC. R 2903.9.3.
  
 9. ON SHEET P100 UNDER NOTES, IT REFERS TO THE 2017 FBC
 CODE, AND THE CURRENT IS 2020. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, DESCRIBING THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  