| 2021-09-20 13:07:15 | 09/20/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLUMBING ISOMETRIC FOR MASTER BATH DOES NOT MATCH |
| | THE LAYOUT, PLEASE SHOW THE BATHROOM GROUP ON ITS |
| | SYSTEM AND NOT IN THE TRUNK LINE DISCHARGE AND PLEAS |
| | SIZE THE DISCHARGE FOR THE WASHING MACHINE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL |
| | PLUMBING. |
| | |
| | 2. THE WASHING MACHINE SHUT-OFF VALVES SHALL BE |
| | ACCESSIBLE WITHOUT MOVING THE UNITS AND WITHIN REACH |
| | PER THE 2017 FBC SEC. R 2903.9.3. |
| | |
| | 3. ON-HOUSE PLAN SHOWING THE LOCATION OF THE TANK-LESS |
| | WATER HEATER SHOWS THE LOCATION AND DISTANCE OF ANY |
| | OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| | HEATER. THE SITE OF THE WATER HEATER SHALL COMPLY WITH |
| | THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE |
| | PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| | 403.5.3. |
| | |
| | 5. VALVE UNDER LAV SHALL HAVE SHUT OFF IN AN ACCESSIBLE |
| | LOCATION, VALVES SERVING INDIVIDUAL PLUMBING FIXTURES, |
| | PLUMBING APPLIANCES, RISERS, AND BRANCHES SHALL BE |
| | ACCESSIBLE PER THE 2020 P2903.9.3 FIXTURE VALVES AND |
| | ACCESS. |
| | |
| | 6. THE SHOWER VALVES SHALL BE EQUIPPED WITH CONTROL |
| | VALVES OF THE PRESSURE-BALANCE, THERMOSTATIC-MIXING, OR |
| | COMBINATION PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE |
| | TYPES WITH A HIGH LIMIT STOP IN ACCORDANCE WITH ASSE |
| | 1016/ASME A112.1016/CSA B125.16. THE HIGH LIMIT STOP |
| | SHALL BE SET TO LIMIT THE WATER TEMPERATURE TO EXCEED |
| | 120 F. IN-LINE THERMOSTATIC VALVES SHALL NOT BE USED TO |
| | COMPLY WITH THIS SECTION PER THE 2020 FBC R 2708.4 |
| | SHOWER CONTROL VALVES. |
| | |
| | 7. THE HAND-HELD SHOWERS SHALL CONFORM TO ASME |
| | A112.18.1/CSA B125.1. HAND-HELD SHOWERS SHALL PROVIDE |
| | BACKFLOW PROTECTION IN ACCORDANCE WITH ASME |
| | A112.18.1/CSA B125.1 OR SHALL BE PROTECTED AGAINST |
| | BACKFLOW BY A DEVICE COMPLYING WITH ASME A112.18.3 PER |
| | THE 2020 FBC R 2708.5 HAND SHOWERS. |
| | |
| | 8. THE WASHING MACHINE SHUT-OFF VALVES SHALL BE |
| | ACCESSIBLE WITHOUT MOVING THE UNITS AND WITHIN REACH |
| | PER THE 2020 FBC SEC. R 2903.9.3. |
| | |
| | 9. ON SHEET P100 UNDER NOTES, IT REFERS TO THE 2017 FBC |
| | CODE, AND THE CURRENT IS 2020. WOULD YOU PLEASE CORRECT |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, DESCRIBING THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |