Plan Review Notes
Plan Review Notes For Permit 21090540
Permit Number 21090540
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-09-23 10:43:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF REPLACING THE FLOORING
 HOWEVER THERE ARE NO SPEC SHEET FOR THE FLOOR
 UNDERLAYMENT, NOR ACTUAL PROPOSED FLOORING.
  
 TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT
 CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE
 VINYL/LAMINATE ETC AND IS MANUFACTURED
 AROUND THE WORLD AND NOT ALL ARE TESTED AND MEETING
 LISTED AND NFPA STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC
 FLOORING TYPE AND/OR PRODUCT SPEC SHEETS OF THE
 PROPOSED FINISHED FLOORING INDICATING THE FIRE BEHAVIOR
 RATING.
  
  
 2) THE FLOOR PLAN SUBMITTED INDICATES THE LOCATION OF
 THE BATHROOM & KITCHEN THAT APPEAR TO BE LOCATED ALONG
 A
 FIRE RATED TENANT AND/OR CORRIDOR SEPARATION WALL
 REQUIRING MAINTENANCE/REPAIR OF THE FIRE RATED WALL
 SHOULD THE DEMO DAMAGE THAT WALL.
  
 PLEASE REVIEW, ENSURE WALL FIRE RATING IS NOT
 COMPROMISED AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON
 THE FLOOR PLAN.
  
  
  
 3) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 ALL FIRE SPRINKLER & FIRE ALARM WORK. INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEDGEMENT ON THE FLOOR PLAN.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]