Plan Review Notes
Plan Review Notes For Permit 21090526
Permit Number 21090526
Review Stop P
Sequence Number 2
Notes
Date Text
2022-02-08 15:59:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090526 3200 45TH ST
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER AND MUST BE TESTED AND CERTIFIED BY THE CITY
 OF WEST PALM BEACH UTILITIES DEPT PER THE CITY OF WEST
 PALM BEACH CROSS CONNECTION CONTROL MANUAL
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6, CLEARLY INDICATE ON ID101 PLAN AND
 ELEVATION DETAILS FOR NEW TOILET ROOM, THE FOLLOWING:
 ...J )SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1
 OR 304.3.2. PARTIALLY COMPLIED
 SECOND REQUEST: ID.101/DETAIL 16; THE REQUESTED 60 INCH
 TURNING SPACE IS NOTED; PER WPB FBC 107.2.1, PLEASE
 SHOW THE TURNING SPACE ON THE PLAN.
 ...K) SHOW CLEAR FLOOR SPACES FOR DRINKING FOUNTAIN AND
 LAVATORY. THE CLEAR FLOOR OR GROUND SPACE SHALL BE 30
 INCHES (760 MM) MINIMUM BY 48 INCHES (1220 MM) MINIMUM
 AND COMPLY WITH FBC ACC SECTION 305. PARTIALLY COMPLIED
 SECOND REQUEST: ID.101/DETAIL 16; THE REQUESTED 30 INCH
 BY 48 INCH CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAIN
 IS NOTED; PER WPB FBC 107.2.1, PLEASE SHOW THE CLEAR
 FLOOR SPACE ON THE PLAN.
  
 4. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER
 DETAIL.COMPLIED
 NEW COMMENT: REGARDING PIPE HANGER DETAIL; INCLUDE PVC
 AS WELL AS NOTED CPVC.
  
 11. PER WPB FBC 107.2.1 AND 107.3.5.1.3(13), PROVIDE A
 WATER RISER DIAGRAM. COMPLIED
 NEW COMMENT: PER FBC PL 606.2, PROVIDE SHUTOFF VALVES
 ON THE WATER SUPPLY FOR EACH HOSE BIB. SHOW ON PLAN
 VIEW AND RISER DIAGRAM.
  
 14. PER WPB FBC 107.2.1, PROVIDE MINIMUM SLOPE
 REQUIREMENTS FOR HORIZONTAL SANITARY PIPING. SHOW
 COMPLIANCE WITH FBC PL 704.1. PARTIALLY COMPLIED
 NEW COMMENT: PER FBC PL 704.1, MINIMUM SLOPE FOR
 HORIZONTAL SANITAEY PIPING 3 INCH AND LARGER IS 1/8
 INCH PER FOOT. SMALLER THAN 3 INCH IS 1/4 INCH PER
 FOOT. PER WPB FBC 107.2.1, PROVIDE THIS CLARIFICATION.
  
 17. PER WPB 107.2 AND FBC PL M314.2, PROVIDE A
 CONDENSATE DRAINAGE SYSTEM(S), PLAN VIEW FOR THE AIR
 HANDLERS. COMPLY WITH FBC PL SECTION 314. INCLUDE
 MATERIAL SPECIFICATION FOR PIPE AND INSULATION, DETAIL
 FOR TERMINATION TO EXTERIOR DRYWELL OR STORM. PLEASE
 NOTE THAT PER WPB CODE OF ORDINANCE CHAPTER 90, ARTICLE
 3, SECTION 90-12B5, A/C CONDENSATE (I INTERPRET THIS AS
 ANY CONDENSATION FROM EVAPORATOR COILS) SHALL NOT
 DISCHARGE TO THE CITY UTILITIES SANITARY SEWAGE
 INFRASTRUCTURE WITHOUT PERMISSION FROM THE UTILITIES
 DEPARTMENT. PARTIALLY COMPLIED
 NEW COMMENT: REGARDING TERMINATION OF CONDENSATE DRAIN,
 FBC PL (M)314.2.1 PROHIBITS CONDENSATE FROM DISCHARGING
 INTO A STREET, ALLEY OR OTHER AREAS SO AS TO CREATE A
 NUISANCE. AS PREVIOUSLY REQUESTED IN REVIEW 1, COMMENT
 17, PLEASE PROVIDE DRYWELL AND DETAIL FOR TERMINATION
 OF THE CONDENSATE DRAIN.
  
 18.NEW COMMENT: A101 AND ID101 FLOOR PLANS HAVE BEEN
 REVISED; PLUMBING FIXTURES HAVE BEEN RELOCATED. P1.10,
 P1.11 AND P200 RISER DIAGRAMS DO NOT REFLECT THE
 CHANGES. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE THE
 DRAWINGS. NOTE THAT THE BATHROOM FLOOR DRAIN MAY BE
 CONNECTED TO THE VENTED WATER CLOSET FIXTURE DRAIN AND
 WET VENTED BY THE VENTED WATER CLOSET AS ALLOWED BY FBC
 PL 912.1. GENERAL PLUMBING NOTES ADDED ON P1.11 IN
 RESPONSE TO REVIEW 1 COMMENTS 8 AND 9 MAY NEED TO BE
 MODIFIED.
  
 19.NEW COMMENT: PER FBC PL 1002.4.1, SPECIFY AND
 PROVIDE DETAIL FOR TRAP SEAL PROTECTION FOR THE
 JANITOR'S ROOM FLOOR SINK SHOWING COMPLIANCE WITH ONE
 OF THE METHODS IN FBC PL 1002.4.1.1 THROUGH 1002.4.1.4.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090526 3200 45TH ST