| 2022-02-08 15:59:02 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21090526 3200 45TH ST |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW |
| | PREVENTER AND MUST BE TESTED AND CERTIFIED BY THE CITY |
| | OF WEST PALM BEACH UTILITIES DEPT PER THE CITY OF WEST |
| | PALM BEACH CROSS CONNECTION CONTROL MANUAL |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6, CLEARLY INDICATE ON ID101 PLAN AND |
| | ELEVATION DETAILS FOR NEW TOILET ROOM, THE FOLLOWING: |
| | ...J )SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1 |
| | OR 304.3.2. PARTIALLY COMPLIED |
| | SECOND REQUEST: ID.101/DETAIL 16; THE REQUESTED 60 INCH |
| | TURNING SPACE IS NOTED; PER WPB FBC 107.2.1, PLEASE |
| | SHOW THE TURNING SPACE ON THE PLAN. |
| | ...K) SHOW CLEAR FLOOR SPACES FOR DRINKING FOUNTAIN AND |
| | LAVATORY. THE CLEAR FLOOR OR GROUND SPACE SHALL BE 30 |
| | INCHES (760 MM) MINIMUM BY 48 INCHES (1220 MM) MINIMUM |
| | AND COMPLY WITH FBC ACC SECTION 305. PARTIALLY COMPLIED |
| | SECOND REQUEST: ID.101/DETAIL 16; THE REQUESTED 30 INCH |
| | BY 48 INCH CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAIN |
| | IS NOTED; PER WPB FBC 107.2.1, PLEASE SHOW THE CLEAR |
| | FLOOR SPACE ON THE PLAN. |
| | |
| | 4. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER |
| | DETAIL.COMPLIED |
| | NEW COMMENT: REGARDING PIPE HANGER DETAIL; INCLUDE PVC |
| | AS WELL AS NOTED CPVC. |
| | |
| | 11. PER WPB FBC 107.2.1 AND 107.3.5.1.3(13), PROVIDE A |
| | WATER RISER DIAGRAM. COMPLIED |
| | NEW COMMENT: PER FBC PL 606.2, PROVIDE SHUTOFF VALVES |
| | ON THE WATER SUPPLY FOR EACH HOSE BIB. SHOW ON PLAN |
| | VIEW AND RISER DIAGRAM. |
| | |
| | 14. PER WPB FBC 107.2.1, PROVIDE MINIMUM SLOPE |
| | REQUIREMENTS FOR HORIZONTAL SANITARY PIPING. SHOW |
| | COMPLIANCE WITH FBC PL 704.1. PARTIALLY COMPLIED |
| | NEW COMMENT: PER FBC PL 704.1, MINIMUM SLOPE FOR |
| | HORIZONTAL SANITAEY PIPING 3 INCH AND LARGER IS 1/8 |
| | INCH PER FOOT. SMALLER THAN 3 INCH IS 1/4 INCH PER |
| | FOOT. PER WPB FBC 107.2.1, PROVIDE THIS CLARIFICATION. |
| | |
| | 17. PER WPB 107.2 AND FBC PL M314.2, PROVIDE A |
| | CONDENSATE DRAINAGE SYSTEM(S), PLAN VIEW FOR THE AIR |
| | HANDLERS. COMPLY WITH FBC PL SECTION 314. INCLUDE |
| | MATERIAL SPECIFICATION FOR PIPE AND INSULATION, DETAIL |
| | FOR TERMINATION TO EXTERIOR DRYWELL OR STORM. PLEASE |
| | NOTE THAT PER WPB CODE OF ORDINANCE CHAPTER 90, ARTICLE |
| | 3, SECTION 90-12B5, A/C CONDENSATE (I INTERPRET THIS AS |
| | ANY CONDENSATION FROM EVAPORATOR COILS) SHALL NOT |
| | DISCHARGE TO THE CITY UTILITIES SANITARY SEWAGE |
| | INFRASTRUCTURE WITHOUT PERMISSION FROM THE UTILITIES |
| | DEPARTMENT. PARTIALLY COMPLIED |
| | NEW COMMENT: REGARDING TERMINATION OF CONDENSATE DRAIN, |
| | FBC PL (M)314.2.1 PROHIBITS CONDENSATE FROM DISCHARGING |
| | INTO A STREET, ALLEY OR OTHER AREAS SO AS TO CREATE A |
| | NUISANCE. AS PREVIOUSLY REQUESTED IN REVIEW 1, COMMENT |
| | 17, PLEASE PROVIDE DRYWELL AND DETAIL FOR TERMINATION |
| | OF THE CONDENSATE DRAIN. |
| | |
| | 18.NEW COMMENT: A101 AND ID101 FLOOR PLANS HAVE BEEN |
| | REVISED; PLUMBING FIXTURES HAVE BEEN RELOCATED. P1.10, |
| | P1.11 AND P200 RISER DIAGRAMS DO NOT REFLECT THE |
| | CHANGES. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE THE |
| | DRAWINGS. NOTE THAT THE BATHROOM FLOOR DRAIN MAY BE |
| | CONNECTED TO THE VENTED WATER CLOSET FIXTURE DRAIN AND |
| | WET VENTED BY THE VENTED WATER CLOSET AS ALLOWED BY FBC |
| | PL 912.1. GENERAL PLUMBING NOTES ADDED ON P1.11 IN |
| | RESPONSE TO REVIEW 1 COMMENTS 8 AND 9 MAY NEED TO BE |
| | MODIFIED. |
| | |
| | 19.NEW COMMENT: PER FBC PL 1002.4.1, SPECIFY AND |
| | PROVIDE DETAIL FOR TRAP SEAL PROTECTION FOR THE |
| | JANITOR'S ROOM FLOOR SINK SHOWING COMPLIANCE WITH ONE |
| | OF THE METHODS IN FBC PL 1002.4.1.1 THROUGH 1002.4.1.4. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21090526 3200 45TH ST |