Plan Review Notes
Plan Review Notes For Permit 21090526
Permit Number 21090526
Review Stop M
Sequence Number 1
Notes
Date Text
2021-10-07 06:11:341ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21090526
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.00: THE REQUIRED OUTDOOR AIR FOR THE NET
 2066 SQ FT OF THE SALES AREA IS 480 CFM?S. FBC
 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  