| 2021-10-21 13:59:11 | NEW COMMERCIAL BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | 1) PLEASE PROVIDE AN ORIGINAL COPY OF THE SOIL REPORT |
| | AS SHOWN ON THE DRAWINGS. FBC WPB 107.3.5.1 |
| | |
| | 2) PLEASE SHOW THE MOP SINK WALL FINISHES TO COMPLY |
| | WITH FBC 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, |
| | |
| | 3) ACCESSIBLE RESTROOM - PLEASE SHOW THE LOCATION |
| | DIMENSIONS FOR THE REAR GRAB FROM THE CENTER OF THE |
| | TOILET PER FBC A 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR HEIGHT |
| | FROM THE FINISHED FLOOR TO THE "REFLECTIVE SURFACE" PER |
| | FBC A 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 5) DRAWING A 301 SHOWS A DOOR PRODUCT APPROVAL |
| | (FL11537.1) THE 8.7 LOCATION NUMBER IS INCORRECT - |
| | SHOULD BE 8.5 - PLEASE PROVIDE A COMPLETE COPY OF THE |
| | PRODUCT APPROVAL (FL11537.1) |
| | |
| | 6) THERE IS A PRODUCT APPROVAL PROVIDED (FL23223) - NO |
| | LOCATION SHOWN FOR THIS DOOR - PLEASE PROVIDE A |
| | LOCATION FOR THIS DOOR. |
| | |
| | 7) A SEPARATE PERMIT IS REQUIRED FOR THE PARKING LOT - |
| | PLEASE ACKNOWLEDGE THIS. |
| | |
| | 8) SOME OF THE METAL BUILDING DETAILS HAVE BEEN |
| | PROVIDED - THIS DOES NOT APPEAR TO BE A COMPLETE METAL |
| | BUILDING PACKAGE - THERE ARE NO FRAMING DETAILS - THE |
| | DRAWINGS ARE NOT SIGNED AND SEALED - THE METAL BUILDING |
| | DRAWINGS NEED TO BE REVIEWED AND MARKED APPROVED BY THE |
| | BUILDING DESIGNER OF RECORD. FBC WPB 107.3.4 |
| | |