| 2021-11-23 11:15:02 | RESIDENTIAL (R3) SHUTTERS, SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21090525 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS |
| | REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE |
| | DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE. |
| | SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED. |
| | ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE |
| | REQUIRED INFORMATION IS PROVIDED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | RESPONSE: |
| | BASED ON SHUTTERS PRODUCT APPROVAL FL12549-R7 THE |
| | INSTALLATION SCHEDULE NEEDS TO BE REVISED. SEC. 107.2.1 |
| | CITY AMENDMENTS: |
| | A) 2" ITW TAPCON DOESN'T PROVIDE 1-3/4" EMBEDMENT INTO |
| | CONCRETE AS REQUIRED BY ANCHOR SCHEDULE ON SHEET 11 OF |
| | 12. |
| | B) DESIGN PRESSURES DON'T MATCH THOSE SHOWN ON THE |
| | DESIGN PRESSURES CHART SUBMITTED. |
| | NOTE: BASED ON THE DESIGN PRESSURES CHART SUBMITTED |
| | NEED TO USE THE 60PSF DESIGN PRESSURES TO DETERMINE THE |
| | ANCHOR SPACING. |
| | C) BOTTOM OF OPENING IS CONCRETE BLOCK. NEED TO USE THE |
| | CONCRETE BLOCK ANCHOR SCHEDULE. REVISE ANCHOR SPACING |
| | AS REQUIRED. |
| | NOTE: BASED ON ON THE ANCHOR SCHEDULE ON SHEET 12 OF 12 |
| | IT LOOKS LIKE THE 1/4" ITW TAPCON CAN NOT BE USED. |
| | REVISE AS REQUIRED. NEED TO USE ANOTHER FASTENER TYPE. |
| | |
| | NOTE: |
| | MINIMUM EDGE DISTANCE EXCLUDES STUCCO FINISH. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |