| 2021-10-25 15:46:15 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21090525 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS |
| | REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE |
| | DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE. |
| | SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED. |
| | ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE |
| | REQUIRED INFORMATION IS PROVIDED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | |
| | 2- RAMMS ENGINEERING, INC. DESIGN PRESSURES |
| | CALCULATIONS SUBMITTED: |
| | A) CALCULATIONS NEED THE ORIGINAL SEAL AND SIGNATURE OF |
| | THE ENGINEER AS REQUIRED BY CHAPTER 471 FLORIDA |
| | STATUTES WHEN SUBMITTING DOCUMENTS/PLANS FOR PUBLIC |
| | RECORDS. |
| | NOTE: SUBMIT CALCULATIONS ELECTRONICALLY WITH |
| | ENGINEER'S DIGITAL SIGNATURE OR PROVIDE HARD COPY |
| | CALCULATIONS WITH ENGINEER'S ORIGINAL SEAL AND |
| | SIGNATURE. |
| | |
| | B)CURRENT BUILDING CODE IS 2020 FBC NOT 2017. AND, 2020 |
| | FBC REFERENCES THE ASCE 7-16 NOT ASCE 7-10. ENGINEER TO |
| | REVISE CALCULATIONS. |
| | CHAPTER 553 F.S. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |