| 2022-03-01 16:42:14 | FS553.791 PRIVATE PROVIDER PLAN REVIEW COMPLIANCE | | | AFFIDAVIT. | | | | | | 1- PRIVATE PROVIDER PLAN REVIEW COMPLIANCE AFFIDAVIT | | | DATED 2/23/2022: | | | A)NOA 18-0502.03 IS A ROOFING UNDERLAYMENT NOT AND ALUM | | | WINDOW WALL SYSTEM AS SPECIFIED ON THE AFFIDAVIT. | | | REVISE AS REQUIRED TO MATCH. | | | | | | 2- PRIVATE PROVIDER PLAN REVIEW COMPLIANCE AFFIDAVIT | | | DATED 2/21/2022: | | | A)DRAWING M.1 UPLOADED TO PROJECTDOX HAS A REVISION #2 | | | DATED 1/17/22. AFFIDAVIT STATES 9/27/2021. REVISE AS | | | REQUIRED TO MATCH M.1 DRAWING. | | | | | | B)DRAWING M.2 UPLOADED TO PROJECTDOX HAS A REVISION #1 | | | DATED 9/27/21. AFFIDAVIT STATES DATED 1/17/2022. REVISE | | | AS REQUIRED TO MATCH M.2 DRAWING. | | | | | | C)HVAC LOAD CALCULATIONS DON'T HAVE THE PREPARATION | | | DATE. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|