Plan Review Notes
Plan Review Notes For Permit 21090499
Permit Number 21090499
Review Stop E
Sequence Number 2
Notes
Date Text
2022-02-07 15:19:37ELECTRIC AUDIT FAILED
 1) ELECTRICAL RISER DIAGRAM DETAILS GENERATOR TRANSFER
 SWITCHES ON LOAD SIDE OF BRANCH CIRCUIT PANELS WITHOUT
 DETAILING HOW SYSTEM WILL BE USED TO TRANSFER FROM
 NORMAL TO STANDBY POWER. PLEASE CORRECT WITH PROPER
 ELECTRICAL RISER DIAGRAM. NEC 215.5 IT APPEARS THE
 ORIGINAL DRAWING WAS CHANGED, UNNECESSARILY AS IT WAS
 CORRECT, EXCEPT FOR THE COMMENTS BELOW
 2) ELECTRICAL RISER DIAGRAM DETAILS AN EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN THE METER AND THE FIRST
 MEANS OF DISCONNECT. PLEASE REMOVE THIS DETAIL TO
 COMPLY WITH NEC 250.30
 3) ELECTRICAL RISER DIAGRAM DETAILS A #4 CU GROUNDING
 ELECTRODE CONDUCTOR FOR A 300-AMP SERVICE WITH 350 MCM
 SERVICE CONDUCTORS. PROPER GROUNDING ELECTRODE
 CONDUCTOR SIZED AS PER NEC 250.66 SHOULD BE A #2 CU
 CONDUCTOR. PLEASE CORRECT AS NOTED
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  