| 2022-02-07 15:19:37 | ELECTRIC AUDIT FAILED |
| | 1) ELECTRICAL RISER DIAGRAM DETAILS GENERATOR TRANSFER |
| | SWITCHES ON LOAD SIDE OF BRANCH CIRCUIT PANELS WITHOUT |
| | DETAILING HOW SYSTEM WILL BE USED TO TRANSFER FROM |
| | NORMAL TO STANDBY POWER. PLEASE CORRECT WITH PROPER |
| | ELECTRICAL RISER DIAGRAM. NEC 215.5 IT APPEARS THE |
| | ORIGINAL DRAWING WAS CHANGED, UNNECESSARILY AS IT WAS |
| | CORRECT, EXCEPT FOR THE COMMENTS BELOW |
| | 2) ELECTRICAL RISER DIAGRAM DETAILS AN EQUIPMENT |
| | GROUNDING CONDUCTOR BETWEEN THE METER AND THE FIRST |
| | MEANS OF DISCONNECT. PLEASE REMOVE THIS DETAIL TO |
| | COMPLY WITH NEC 250.30 |
| | 3) ELECTRICAL RISER DIAGRAM DETAILS A #4 CU GROUNDING |
| | ELECTRODE CONDUCTOR FOR A 300-AMP SERVICE WITH 350 MCM |
| | SERVICE CONDUCTORS. PROPER GROUNDING ELECTRODE |
| | CONDUCTOR SIZED AS PER NEC 250.66 SHOULD BE A #2 CU |
| | CONDUCTOR. PLEASE CORRECT AS NOTED |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |