2021-12-29 15:13:50FAILED ELECTRICAL AUDIT FOR THE FOLLOWING
 1) INCORRECT SIZE GROUNDING ELECTRODE CONDUCTOR NEC
 250.66
 2) INCORRECT SIZE MAIN BONDING JUMPER CONDUCTOR NEC
 250.102
 3) INCORRECT LOAD CALCULATION, MANY FASTENED IN PLACE
 APPLIANCES NOT LISTED NEC 220.82(B)(3)
 4) INCORRECT LOAD CALCULATION, HEAT IS LISTED AT 20KW
 FOR (3) 10KW HEAT STRIPS. COOLING SHOULD BE USED
 INSTEAD PER NEC 220.82? ?THE LARGEST OF THE SIX
 SELECTIONS. COOLING @ 100% LISTED AT 9.6KW EACH
  