| Date |
Text |
| 2021-12-29 15:13:50 | FAILED ELECTRICAL AUDIT FOR THE FOLLOWING | | | 1) INCORRECT SIZE GROUNDING ELECTRODE CONDUCTOR NEC | | | 250.66 | | | 2) INCORRECT SIZE MAIN BONDING JUMPER CONDUCTOR NEC | | | 250.102 | | | 3) INCORRECT LOAD CALCULATION, MANY FASTENED IN PLACE | | | APPLIANCES NOT LISTED NEC 220.82(B)(3) | | | 4) INCORRECT LOAD CALCULATION, HEAT IS LISTED AT 20KW | | | FOR (3) 10KW HEAT STRIPS. COOLING SHOULD BE USED | | | INSTEAD PER NEC 220.82? ?THE LARGEST OF THE SIX | | | SELECTIONS. COOLING @ 100% LISTED AT 9.6KW EACH | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|