Plan Review Notes
Plan Review Notes For Permit 21090499
Permit Number 21090499
Review Stop B
Sequence Number 1
Notes
Date Text
2021-12-30 10:55:44NEW SINGLE FAMILY RESIDENCE (R3) AUDIT COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21090499
  
 1- MISSING LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING: R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 2- SHEET A-1:
 A)WIND DESIGN DATA SPECIFIES EXPOSURE "B". ACCORDING TO
 SEC. R301.2.1.4.3 FBC-RESIDENTIAL THIS BUILDING IS
 LOCATED IN EXPOSURE "C" NOT "B". REVISE EXPOSURE IN ALL
 PLANS.
 NOTE: REVISE DOORS, WINDOWS, ROOF DESIGN PRESSURES
 ACCORDINGLY. AND, VERIFY ALL PRODUCT APPROVALS FOR
 COMPLIANCE BEFORE SUBMITTAL.
  
 B)FLOOR PLAN SHOWS A FIRE PIT INSIDE THE COVERED PATIO.
 THERE IS NOT INFORMATION ABOUT THIS FIRE PIT. TYPICALLY
 FIRE PITS ARE BUILT OUTSIDE AND AWAY FROM THE BUILDING.
 THERE IS A CONCERN ABOUT FIRE GIVEN THE LOCATION AND
 TYPE OF FIRE PIT TO BE BUILT/INSTALLED. ARCHITECT OF
 RECORD NEEDS TO PROVIDE COMPLETE INFORMATION SHOWING
 THAT PROPOSED INSTALLATION WILL NOT CREATE A FIRE
 HAZARD. PROVIDE COMPLETE INFORMATION, INCLUDING
 MANUFACTURER'S SPECS, FIRE PIT DETAILS/SPECIFICATIONS,
 CLEARANCES, ETC. SEC. 101.3 CITY AMENDMENTS. SEC.
 107.2.1.2 CITY AMENDMENTS.
  
 C)CLARIFY WHY ONLY THE WALLS ADJACENT TO BEDROOM #4 AND
 STORAGE ROOM ARE HATCHED TO BE INSULATED , WHILE THE
 WALL ADJACENT TO THE HALLWAY IS NOT? HALLWAY WALL IS
 ALSO SEPARATING A/C AREA FROM NON A/C AREA. SEC. R103.2
 FBC-ENERGY CONSERVATION.
  
 D)CLARIFY THE PURPOSE COVERED PATIO DOOR #14 SHOWN
 ADJACENT TO THE SLIDING GLASS DOORS BY THE KITCHEN
 AREA. PROVIDE MORE INFORMATION: DOOR TYPE, DESIGN
 PRESSURES, FRAMING, PRODUCT APPROVALS, ETC. SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- SHEET S-1:
 A)THERE ARE NO DETAILS/SPECIFICATIONS FOR COVERED PATIO
 STRUCTURAL COLUMNS. SEC. R301.1 FBC-RESIDENTIAL.
  
 B)ENTRY PORCH CONSTRUCTION IS MISSING INFORMATION.
 THERE IS NO FOOTING FOR THE EXTERIOR WALL SHOWN AT THE
 BOTTOM OF THE ENTRY PORCH. THERE ARE NO
 DETAILS/SPECIFICATIONS FOR THE CONSTRUCTION OF THIS
 WALL EITHER. THERE ARE NO DETAILS/SPECIFICATIONS FOR
 THE CONSTRUCTION OF THE ENTRY FACADE. DETAIL 1/S-5
 DOESN'T PROVIDE COMPLETE INFORMATION. PROVIDE COMPLETE
 EXTERIOR WALL SECTIONS AND DETAILS/SPECIFICATIONS.
 SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL. SEC. 107.3.5.3 CITY AMENDMENTS.
  
 C)FRAMED BEARING WALL BETWEEN OFFICE AND LIVING ROOM IS
 NOT CLEAR. FOUNDATION PLAN AND INTERIOR BEARING WALL
 DETAIL 4/S-3 SPECIFY 2X6 SPF @16"O.C. HOW CAN YOU HAVE
 2X6 STUDS AT 16" O.C. IF PLANS SHOW 11-1/2" COLUMNS
 SPACED AT 5'-0" AND 3'-0"? REVISE AS REQUIRED. PROVIDE
 CORRECT DETAIL/SPECIFICATIONS FOR BEARING WALL IN THIS
 AREA. SEC. R301.1 FBC-RESIDENTIAL. SEC. 107.2.1 CITY
 AMENDMENTS.
 NOTE: SPECIFY TOP AND BOTTOM CONNECTIONS ALSO. INTERIOR
 BEARING WALL DETAIL 4/S-3 ON SHEET S-3 SPECIFIES HUGHES
 TP6X TOP & BOTTOM CONNECTORS. IT IS MY UNDERSTANDING
 HUGHES IS OUT OF BUSINESS AND THIS CONNECTORS ARE NO
 LONGER AVAILABLE. REVISE CONNECTORS AS REQUIRED OR
 PROVIDE COPY OF CURRENT HUGHES CATALOG.
  
 D)DESIGN DATA NOTE #4 SHOWN UNDER FOUNDATION NOTES IS
 MISSING INFORMATION. DESIGNER OF RECORD TO CLEARLY
 SPECIFY ROOF LIVE AND DEAD LOADS (TOP AND BOTTOM
 CHORDS), INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY
 TABLE R301.5 FBC-RESIDENTIAL. NOTE: SEE FOOTNOTES "B"
 AND "G". THIS HOUSE HAS TALL ATTICS.
  
 E)SOIL BEARING PRESSURE IS NOT CLEAR. DESIGN DATA NOTE
 #4 SHOWN UNDER FOUNDATION NOTES AND FOUNDATION NOTE #8
 SPECIFIES 3,000 PSF SOIL BEARING PRESSURE, WHILE
 FOUNDATION NOTE #1 ON SAME FOUNDATION NOTES SPECIFIES
 2,500 PSF. REVISE AS REQUIRED TO MATCH. SEC. R301.1
 FBC-RESIDENTIAL. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- SHEET S-2: THERE IS NOT INFORMATION FOR THE BEAMS AT
 THE COVERED PATIO AND ABOVE ALL OPENINGS. PROVIDE BEAM
 SCHEDULE AND COMPLETE DETAILS/ SPECIFICATIONS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 5-SHEET S-3:
 A)GARAGE BUCK DETAIL IS MISSING INFORMATION. THERE IS
 NOT DETAIL 6/A-10. PROVIDE COMPLETE STRUCTURAL BUCK
 DETAIL. SPECIFY ANCHOR TYPE, SIZE, SPACING AND
 EMBEDMENT. SEC. R301.1 FBC-RESIDENTIAL.
  
 B)REVISE WINDOW/DOOR BUCK DETAIL. 1X4 BUCKS DON'T
 PROVIDE FULL SUPPORT TO THE DOOR FRAME AS REQUIRED BY
 SEC. R609.7.2.1 FBC-RESIDENTIAL.
  
 6- REVISE ROOF SHEATHING NAILING SPACING. ROOF
 SHEATHING NEEDS TO BE NAILED AT 4 INCHES O.C. IN THE
 FIELD AND EDGES AS REQUIRED BY SEC. R803.2.3.1 AND
 TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS ON ALL PLANS AND WALL
 SECTIONS TO AVOID CONFLICTS/DELAYS.
  
 7- PLANS DON'T PROVIDE DETAIL/SPECIFICATIONS FOR
 CEILING CONSTRUCTION AT COVERED PORCH.
 SEC. R703.1.2.1 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH ITEM #2(B) ABOVE.
  
 8- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING R-20 SPRAY ISO. INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 9- ENERGY CALCULATIONS:
 A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 C)NUMBER OF BEDROOMS IS INCORRECT. REVISE ITEM #4. SEC.
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 D)DOORS INFORMATION ON PAGE 3 DOESN'T MATCH PLANS.
 WHERE ARE THE TWO SW INSULATED 3X8 DOORS AND THE NW 3X8
 WOOD DOOR? SEE PLANS AND PRODUCT APPROVALS AND REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 E)WINDOWS INFORMATION ON PAGE 4 DOESN'T MATCH PLANS.
 ORIENTATION OF WINDOWS DON'T MATCH PLANS. SEE SURVEY
 AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 10- PRODUCT APPROVALS
 A)GARAGE DOOR NOA 20-0922.36 IS FOR DOORS WITH A
 MAXIMUM WIDTH OF 9'-0". GARAGE DOORS SPECIFIED ON PLANS
 ARE BIGGER. NEED ANOTHER PRODUCT APPROVAL FOR SPECIFIED
 LARGER SIZE. FAC 61G20-3.001.
  
 B)MISSING PRODUCT APPROVALS FOR ALL TYPES OF WINDOWS
 SHOWN ON PLANS. FAC 61G20-3.001
  
 C) WINDOW AND DOOR MULLIONS NOA 20-0814.10 NEED TO
 SPECIFY MULLION SIZES TO BE USED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 D)ROOF TILE NOA 16-0711.05 DOESN'T SPECIFY TILE
 FASTENING METHOD. UNABLE TO VERIFY IF PROPOSED
 INSTALLATION WILL MEET THE REQUIRED UPLIFT. SEC.
 R301.2.1 FBC-RESIDENTIAL.
 NOTE: IF PROPOSED INSTALLATION IS SCREWS, THEN SPECIFY
 SIZE AND NUMBER OF SCREWS. IF SPECIFYING ROOF TILE
 ADHESIVE, THEN SPECIFY PADDY SIZE AND PRODUCT APPROVAL
 IS REQUIRED.
  
 11-DESIGNER OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  