| Plan Review Notes For Permit 21090470 |
| Permit Number |
21090470 |
|
| Review Stop |
Z |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2022-04-26 15:32:09 | FAILED | | | | | | 1) REPEAT COMMENT: PROVIDE THE CROSS SECTION OF THE | | | UNDERGROUND ELECTRIC (BORING PROFILE) SO THAT STAFF CAN | | | VERIFY THAT THE BORE IS DEEP ENOUGH TO AVOID DAMAGING | | | THE ROOT SYSTEMS OF THE TREES OVER THE ELECTRIC PATH. | | | BORE PITS/HANDHOLES NEED TO BE SHOWN AT LEAST 10 FEET | | | FROM THE EXISTING TREES. THESE TREES ARE REQUIRED | | | LANDSCAPE BUFFER TREES TO IT NEEDS TO BE SHOWN THAT | | | THIS INSTALLATION PROVIDES ENOUGH SEPARATION TO NOT | | | DAMAGE THE ROOT SYSTEMS OF THE TREES. | | | | | | 2) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. | | | THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP | | | 7042 TRAFFIC GREY A. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|