| 2021-12-03 07:23:28 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. ENGINEERING PREPARED BY TOM TWOMEY, PE REQUIRES THE |
| | FOLLOWING MINIMUM DESIGN PRESSURES: |
| | |
| | WINDOWS, +71.7 / -71.7 |
| | |
| | SLIDING GLASS DOORS - +71.7 / -71.7 |
| | |
| | THE PRODUCT APPROVAL FOR THE WINDOWS (FL 22250) |
| | PROPOSES A WINDOW THAT HAS A DESIGN PRESSURE LIMITATION |
| | OF +60 / -80. THIS DOES NOT MEET THE REQUIREMENT |
| | SPECIFIED BY THE ENGINEER. |
| | |
| | 2. I COULD NOT LOCATE A CURRENT PRODUCT APPROVAL FOR |
| | THE SLIDING GLASS DOOR, FBC B 1609. |
| | |
| | 3. COORDINATE WITH [email protected] TO HAVE ALL |
| | UNNECESSARY DOCUMENTS DELETED. THERE ARE 19 FILES IN |
| | THE SUPPORTING DOCUMENTS FOLDER. FOR PERMIT DOCUMENTS |
| | THERE SHOULD BE: |
| | |
| | ONE LOCATION PLAN (FLOOR PLAN SHOWING LOCATIONS OF |
| | PROPOSED WINDOWS AND SGDS) |
| | ENGINEERING (DESIGN PRESSURES PREPARED BY ENGINEER) |
| | PRODUCT APPROVAL FOR WINDOWS |
| | PRODUCT APPROVAL FOR SLIDING GLASS DOORS |
| | |
| | THEREFORE IN ADDITION TO THE PERMIT APPLICATION, THERE |
| | SHOULD BE FOUR DOCUMENTS. THE DOCUMENTS SHOULD CLEARLY |
| | INDICATE WHICH OPTION IS PROPOSED TO SHOW THAT THE |
| | PROPOSED PRODUCT MEETS THE DESIGN PRESSURES SPECIFIED |
| | BY THE ENGINEER. |
| | |
| | |
| | |
| | |