Plan Review Notes
Plan Review Notes For Permit 21090438
Permit Number 21090438
Review Stop B
Sequence Number 3
Notes
Date Text
2021-12-03 07:23:28****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. ENGINEERING PREPARED BY TOM TWOMEY, PE REQUIRES THE
 FOLLOWING MINIMUM DESIGN PRESSURES:
  
 WINDOWS, +71.7 / -71.7
  
 SLIDING GLASS DOORS - +71.7 / -71.7
  
 THE PRODUCT APPROVAL FOR THE WINDOWS (FL 22250)
 PROPOSES A WINDOW THAT HAS A DESIGN PRESSURE LIMITATION
 OF +60 / -80. THIS DOES NOT MEET THE REQUIREMENT
 SPECIFIED BY THE ENGINEER.
  
 2. I COULD NOT LOCATE A CURRENT PRODUCT APPROVAL FOR
 THE SLIDING GLASS DOOR, FBC B 1609.
  
 3. COORDINATE WITH [email protected] TO HAVE ALL
 UNNECESSARY DOCUMENTS DELETED. THERE ARE 19 FILES IN
 THE SUPPORTING DOCUMENTS FOLDER. FOR PERMIT DOCUMENTS
 THERE SHOULD BE:
  
 ONE LOCATION PLAN (FLOOR PLAN SHOWING LOCATIONS OF
 PROPOSED WINDOWS AND SGDS)
 ENGINEERING (DESIGN PRESSURES PREPARED BY ENGINEER)
 PRODUCT APPROVAL FOR WINDOWS
 PRODUCT APPROVAL FOR SLIDING GLASS DOORS
  
 THEREFORE IN ADDITION TO THE PERMIT APPLICATION, THERE
 SHOULD BE FOUR DOCUMENTS. THE DOCUMENTS SHOULD CLEARLY
 INDICATE WHICH OPTION IS PROPOSED TO SHOW THAT THE
 PROPOSED PRODUCT MEETS THE DESIGN PRESSURES SPECIFIED
 BY THE ENGINEER.
  
  
  
  