| 2021-10-25 06:30:37 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21090434 |
| | 10/25/2021 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE BACKFLOW FOR THE POOL AUTOFILL SYSTEM WILL |
| | REQUIRE A SEPARATE PERMIT. MANUFACTURER'S |
| | SPECIFICATIONS AND A SEPARATE PLUMBING PERMIT SHALL BE |
| | SUBMITTED PRIOR TO THE INSTALLATION OF THE DEVICE. THE |
| | DEVIC MUST BE INSTALLED BY A LICENSED PLUMBING |
| | CONTRACTOR.F.S.489.103. AND MUST PROVIDE A DIFFERENTIAL |
| | TEST REPORT FOR FINAL INSPECTION |
| | |
| | 2) THE SCOPE OF THE PLUMBING TO BE DONE IS UNCLEAR |
| | PLEASE PROVIDE PLUMBING PLAN INCLUDING A SANITARY AND |
| | WATER ISOMETRIC DRAWING. PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | 3) GAS FOR BBQ GRILL IS BEING DONE UNDER 21070798 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |