Plan Review Notes
Plan Review Notes For Permit 21090432
Permit Number 21090432
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-01 06:07:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090432 5107 S DIXIE HWY
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.SEE A-150 DEMO PLAN, NOTE 11. PLEASE CLARIFY. WHAT IS
 MEANT BY CIRCULATION? IS THE CONCRETE BLOCKING BEING
 REMOVED TO PROVIDE A CIRCULATION PATH WHICH WOULD ALLOW
 PATRONS AND EMPLOYEES, TO FREELY MOVE FROM ONE SIDE OF
 THE WALL TO THE OTHER? PER WPB FBC 107.2.1, PROVIDE
 DIMENSIONED DETAIL OF OPENINGS AND SHOW THE ACCESSIBLE
 ROUTE/CIRCULATION PATH FROM THE SEATING AREA ADJACENT
 TO KITCHEN AREA TO THE ACCESSIBLE RESTROOMS. SHOW
 COMPLIANCE WITH FBC ACC SECTION 206 AND FBC PL 403.3.1.
  
 2.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
  
 3.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE
  
 4.MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 603.3.
  
 5.PER WPB FBC 107.2.1, PROVIDE A NOTE STATING ?DRINKING
 WATER SHALL BE PROVIDED IN A FLAT BOTTOM CONTAINER FREE
 OF CHARGE AS ALLOWED BY FBC PL 410.4? OR PROVIDE A
 DRINKING FOUNTAIN THAT COMPLIES WITH FBC PL 410.3, FBC
 ACC 307 AND FBC 602.
  
 6.PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR GAS
 TANKLESS WATER HEATER. THE INSTALLATION MANUAL SHALL BE
 ONSITE AT THE TIME OF INSPECTION.
  
 7.PER WPB FBC 107.2.1, SPECIFY THE PRESSURE RELIEF
 VALVE ON THE HOT WATER PIPING OUT OF THE TANKLESS WATER
 HEATER OR REQUIRE FURNISHING OF NAVIEN OPTION (INCLUDE
 PART NUMBER) FOR RELIEF VALVE IN THE WATER HEATER
 DETAIL NOTES.
 ?6.A) PER WPB FBC 107.2.1 PROVIDE SIZE, ROUTING AND
 TERMINATION POINT OF THE WATER HEATER RELIEF VALVES
 DISCHARGE PIPING. COMPLY WITH FBC PL 504.6.1 THROUGH
 504.6.14. PLEASE NOTE, THE PIPING MAY NOT DISCHARGE TO
 THE MOP SINK PER FBC PL 504.6.5.
  
 8.A-601 SHOWS A CONCRETE SLAB REPAIR DETAIL; P-4.1
 SHOWS A TRAP PRIMER DETAIL WITH WHAT APPEARS TO BE
 WOODEN JOIST SYSTEM. PER WPB FBC 107.2.1, PLEASE
 CLARIFY.
  
 9.PER WPB FBC 107.2.1, PROVIDE DETAIL SHOWING HOW
 RESEAL WATER FOR MULTIPLE FLOOR DRAIN TRAPS FROM ONE
 DEVICE WILL BE PROPERLY DISTRIBUTED TO ALLOW EACH TRAP
 TO BE RESEALED IN ACCORDANCE WITH FBC PL 1002.4.1.3.
  
 10.RE: A-202; PER WPB FBC 107.2.1, PROVIDE ON THE
 FIXTURE/FURNITURE/EQUIPMENT SCHEDULE, ALL APPLICABLE
 PLUMBING WATER & DRAINAGE CONNECTIONS, SIZED, INDICATE
 INDIRECT OR DIRECT DRAIN CONNECTIONS, REQUIRED BACKFLOW
 PREVENTERS (WHERE REQUIRED, SPECIFY TYPE AND MODEL),
 AIR GAPS, PRESSURE REDUCERS (WHERE REQUIRED, SPECIFY
 TYPE AND MODEL)/GAS CONNECTION SIZE AND BTUS/ELECTRICAL
 CHARACTERISTICS. SOME APPEAR TO BE ADDRESSED ON P0.1
 SCHEDULE, OTHERS ARE NOT.
  
 11.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR WATER
 CONNECTION TO F-2 WATER FILTER, F-4 BOIL KETTLE AND
 F-15 MASH LAUDER TUN. INCLUDE REQUIRED BACKFLOW
 PREVENTERS (WHERE REQUIRED, SPECIFY TYPE AND MODEL),
 PRESSURE REDUCERS (WHERE REQUIRED, SPECIFY TYPE AND
 MODEL).
  
 12.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR EMERGENCY
 EYEWASH, INCLUDING MOUNTING HEIGHT AND ANCHORING
 DETAILS. PER WPB FBC SHOW COMPLIANCE WITH FBC ACC
 307.2, PROTRUDING OBJECTS. OBJECTS WITH LEADING EDGES
 MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE
 THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY INTO THE CIRCULATION PATH.
  
 13.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 14. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SUPPORT OF
 WALL MOUNTED WATER HEATERS
  
 15. PER WPB FBC 107.2.1, PROVIDE DRYWELL DETAIL.
  
 16. PER WPB FBC 107.2.1, PROVIDE REFERENCE SCHEMATIC(S)
 OF GLYCOL AND C02 SYSTEMS. PROVIDE DETAILS FOR MAKE-UP
 WATER IF APPLICABLE.
  
 17.P3.1 SANITARY ISOMETRIC FOR RESTROOMS. PER FBC PL
 914.2, PROVIDE A CIRCUIT VENT CONNECTION DOWNSTREAM OF
 THE MOST UPSTREAM WATER CLOSET NOT DOWNSTREAM OF THE
 UPSTREAM LAVATORY. IN LIEU OF THAT, THE ENTIRE LENGTH
 OF THE VENT SECTION OF THE HORIZONTAL BRANCH DRAIN
 SHALL BE SIZED FOR THE TOTAL DRAINAGE DISCHARGE TO THE
 BRANCH PER 914.3. PLEASE NOTE THAT PER 914.5, FIXTURES,
 OTHER THAN THE CIRCUIT-VENTED FIXTURES, ARE PERMITTED
 TO DISCHARGE TO THE HORIZONTAL BRANCH DRAIN. SUCH
 FIXTURES SHALL BE LOCATED ON THE SAME FLOOR AS THE
 CIRCUIT-VENTED FIXTURES AND SHALL BE EITHER
 INDIVIDUALLY OR COMMON VENTED.
 ?17.A)PER 914.4, PROVIDE A RELIEF VENT DOWNSTREAM OF
 THE LAST TWO WATER CLOSETS ON THE CIRCUIT VENTED
 BRANCH.
  
 18. P3.1 SANITARY ISOMETRIC FOR MOP SINK AND EMERGENCY
 EYEWASH: PER WPB FBC 107.2.1, PROVIDE NOTE STATING ?MOP
 SINK COMMON VENTED BY EYEWASH PER FBC PL 911.3?
  
 19. P3.1 SANITARY ISOMETRIC FOR BREWERY/BAR FLOOR
 DRAINS: PER WPB FBC 107.2.1, PROVIDE NOTE STATING
 ?BREWERY/BAR FLOOR DRAINS AND FLOOR SINKS VENTED BY
 COMBINATION WASTE AND VENT IN ACCORDANCE WITH FBC PL
 SECTION 915.?
  
 20. BREWERY FLOOR DRAINS ARE TRENCH DRAINS. PER WPB FBC
 107.2.1, PROVIDE SPEC AND ADD TO SCHEDULE.
  
 21. IT IS NOTED THAT THE HOT WATER TO THE PUBLIC
 BATHROOMS HAS AN ISOLATION VALVE IN THE LINE. THIS IS A
 RECIRCULATED LINE WHICH WILL NOT FUNCTION IF THE
 ISOLATION VALVE IS CLOSED. PLEASE NOTE THAT THE
 REQUIREMENT FOR A FULL OPEN VALVE AS NOTED IN FBC PL
 606.1(5) IS NOT APPLICABLE AS WPB BUILDING FOLLOWS THE
 INTERPRETATION OF IBC PLUMBING COMMENTARY 606.1(5)
 WHICH STATES A WATER PIPE EXTENDING VERTICALLY THROUGH
 ONE OR MORE FLOORS AND CONVEYING WATER VERTICALLY
 DOWNWARD IS CONSIDERED A DOWN-FEED. VALVES AT THE TOP
 OF DOWN-FEEDS ARE HELPFUL FOR SERVICING MULTI-STORY
 BUILDING SO THAT ONLY SMALL AREAS OF THE BUILDING WILL
 BE WITHOUT WATER TO FACILITATE REPAIRS IN ONE AREA.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090432 5107 S DIXIE HWY
  
  