| 2021-09-29 06:12:41 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21090432 5107 S DIXIE HWY |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS: DENIED |
| | |
| | 1.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2020 FUEL GAS CODE SEC. 402.2, AND 301.3. GAS |
| | APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| | SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 2.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR GAS |
| | SHUT OFF VALVES AND APPLIANCE VALVES. VALVES SHALL |
| | COMPLY WITH FBC FG SECTION 409.1.1 AND TABLE 409.1.1. |
| | |
| | 3.ACCORDING TO THE PLUMBING LEGEND ON P0.1, ON P3.1 GAS |
| | RISER, A GAS COCK AND A BALL VALVE ARE IN THE |
| | CONNECTION LINE TO THE BOIL KETTLE, GAS COCKS ARE IN |
| | CONNECTION LINES TO THE TANKLESS HEATERS, BUT ARE SHOWN |
| | AS BALL VALVES IN THE TANKLESS WATER HEATER DETAIL ON |
| | P4.1, AND A BALL VALVE AND GAS COCK ARE IN UPSTREAM |
| | SIDE OF THE GAS METER. PER WPB FBC 107.2.1, PLEASE |
| | CLARIFY. |
| | |
| | 4.RE: P4.1 DETAIL MEDIUM TO LOW PRESSURE GAS REGULATOR |
| | DETAIL; DISTRIBUTION DOWNSTREAM OF THE UTILITY COMPANY |
| | REGULATOR IS ALREADY .5 PSI. IS DELIVERY PRESSURE TO |
| | APPLIANCES TO BE REDUCED AGAIN? IF SO, PER WPB FBC |
| | 107.2.1, INDICATE THE AFFECTED APPLIANCE(S), CLARIFY |
| | AND STATE THE REDUCED PRESSURE. INDICATE ANY ADDITIONAL |
| | TABLES USED IN SIZING. SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION. 2020 FGC SEC.410.1. |
| | PROVIDE IF NOT, DELETE THE DETAIL; DELETE ANY |
| | REGULATORS IN THE RISER DIAGRAM AS WELL. IT IS NOTED |
| | THAT THE TANKLESS WATER HEATER DETAIL DOES NOT INDICATE |
| | ANY MP REGULATORS. |
| | |
| | 5. PER WPB FBC 107.2.1, PROVIDE AN APPLIANCE CONNECTION |
| | DETAIL SHOWING VALVE, UNION(S) AND DIRT LEG. |
| | |
| | 6. PER WPB FBC 107.2.1, PROVIDE A GAS PIPE HANGER AND |
| | WALL STAND-OFF DETAIL WITH A NOTE STATING, " GAS PIPE |
| | SHALL BE SUPPORTED IN ACCORDANCE WITH FBC FG 407.2." |
| | |
| | 7. PER WPB FBC 107.2.1, PROVIDE A GAS EQUIPMENT |
| | SCHEDULE INDICATING LISTING THE BTU LOAD OF EACH |
| | APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| | |
| | 8.PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR |
| | COMBUSTION AIR FOR THE BOIL KETTLE AND THE AVAILABLE |
| | COMBUSTION AIR 9NOT TO BE CONFUSED WITH MAKE-UP AIR) |
| | PER THE 2020 FBC-FUEL GAS CODE SEC.304.1. |
| | |
| | 9. PER WPB FBC 107.2.1, ON THE PLAN SUBMIT A DETAIL |
| | SHOWING THE TYPES, LOCATIONS, SIZE, TERMINATION POINTS, |
| | HEIGHT ABOVE THE ROOF AND ANCHORING DETAILS OF THE GAS |
| | VENT(S) PER 2020 FBC-FUEL GAS SECS. 502 THRU 505. |
| | DETAIL(S) SHALL ALSO COMPLY WITH MANUFACTURERS |
| | RECOMMENDATIONS (SEE NAVIEN COMMON VENT INSTALLATION |
| | GUIDE HTTPS://WWW.NAVIENINC.COM/DOWNLOADS/COMMON-VENT-I |
| | NSTALLATION-MANUAL-EN) |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |