Plan Review Notes
Plan Review Notes For Permit 21090432
Permit Number 21090432
Review Stop G
Sequence Number 1
Notes
Date Text
2021-09-29 06:12:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090432 5107 S DIXIE HWY
  
 1ST REVIEW
 GAS COMMENTS: DENIED
  
 1.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2020 FUEL GAS CODE SEC. 402.2, AND 301.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
  
 2.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR GAS
 SHUT OFF VALVES AND APPLIANCE VALVES. VALVES SHALL
 COMPLY WITH FBC FG SECTION 409.1.1 AND TABLE 409.1.1.
  
 3.ACCORDING TO THE PLUMBING LEGEND ON P0.1, ON P3.1 GAS
 RISER, A GAS COCK AND A BALL VALVE ARE IN THE
 CONNECTION LINE TO THE BOIL KETTLE, GAS COCKS ARE IN
 CONNECTION LINES TO THE TANKLESS HEATERS, BUT ARE SHOWN
 AS BALL VALVES IN THE TANKLESS WATER HEATER DETAIL ON
 P4.1, AND A BALL VALVE AND GAS COCK ARE IN UPSTREAM
 SIDE OF THE GAS METER. PER WPB FBC 107.2.1, PLEASE
 CLARIFY.
  
 4.RE: P4.1 DETAIL MEDIUM TO LOW PRESSURE GAS REGULATOR
 DETAIL; DISTRIBUTION DOWNSTREAM OF THE UTILITY COMPANY
 REGULATOR IS ALREADY .5 PSI. IS DELIVERY PRESSURE TO
 APPLIANCES TO BE REDUCED AGAIN? IF SO, PER WPB FBC
 107.2.1, INDICATE THE AFFECTED APPLIANCE(S), CLARIFY
 AND STATE THE REDUCED PRESSURE. INDICATE ANY ADDITIONAL
 TABLES USED IN SIZING. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. 2020 FGC SEC.410.1.
 PROVIDE IF NOT, DELETE THE DETAIL; DELETE ANY
 REGULATORS IN THE RISER DIAGRAM AS WELL. IT IS NOTED
 THAT THE TANKLESS WATER HEATER DETAIL DOES NOT INDICATE
 ANY MP REGULATORS.
  
 5. PER WPB FBC 107.2.1, PROVIDE AN APPLIANCE CONNECTION
 DETAIL SHOWING VALVE, UNION(S) AND DIRT LEG.
  
 6. PER WPB FBC 107.2.1, PROVIDE A GAS PIPE HANGER AND
 WALL STAND-OFF DETAIL WITH A NOTE STATING, " GAS PIPE
 SHALL BE SUPPORTED IN ACCORDANCE WITH FBC FG 407.2."
  
 7. PER WPB FBC 107.2.1, PROVIDE A GAS EQUIPMENT
 SCHEDULE INDICATING LISTING THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM.
  
 8.PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR
 COMBUSTION AIR FOR THE BOIL KETTLE AND THE AVAILABLE
 COMBUSTION AIR 9NOT TO BE CONFUSED WITH MAKE-UP AIR)
 PER THE 2020 FBC-FUEL GAS CODE SEC.304.1.
  
 9. PER WPB FBC 107.2.1, ON THE PLAN SUBMIT A DETAIL
 SHOWING THE TYPES, LOCATIONS, SIZE, TERMINATION POINTS,
 HEIGHT ABOVE THE ROOF AND ANCHORING DETAILS OF THE GAS
 VENT(S) PER 2020 FBC-FUEL GAS SECS. 502 THRU 505.
 DETAIL(S) SHALL ALSO COMPLY WITH MANUFACTURERS
 RECOMMENDATIONS (SEE NAVIEN COMMON VENT INSTALLATION
 GUIDE HTTPS://WWW.NAVIENINC.COM/DOWNLOADS/COMMON-VENT-I
 NSTALLATION-MANUAL-EN)
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090432 5107 S DIXIE HWY
  