| Plan Review Notes For Permit 21090432 |
| Permit Number |
21090432 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-19 14:16:28 | BUILD OUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE SHOW THE ACCESSIBLE SEATING AT THE BAR - | | | COUNTER HEIGHT, KNEE CLEARANCE, TOE CLEARANCE ETC. - | | | FBC ACCESSIBILITY 226.2 (BUILDING OFFICIALS | | | INTERPRETATION IS THAT ACCESSIBLE SEATING MUST BE | | | PROVIDED AT THE BAR) | | | 2) EXTERIOR COOLER IS SUBJECT TO WIND LOADS FBC 1609 - | | | PLEASE PROVIDE THE EXTERIOR COOLER DETAILS SHOWING WIND | | | DESIGN CRITERIA, PANEL DESCRIPTIONS, ATTACHMENTS, | | | FOUNDATIONS ETC. |
|