Plan Review Notes
Plan Review Notes For Permit 21090354
Permit Number 21090354
Review Stop P
Sequence Number 2
Notes
Date Text
2021-10-06 10:32:3610/06/21 2 ND POOL REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON THE ATDH CALCUUALTION SUBMITTED THE HEAT PUNP NOR
 THE CHLORINATOR WHERE IN THE CALCULATIONS. WOULD YOU
 PLEASE SUBMIT ALL SYSTEM COMPONENTS EXCEPT THE PUMP PER
 THE ANSI/APSP/ICC 7 - 2015 SECS. 4.4.9, 4.4.9.1 MAXIMUM
 SYSTEM FLOW RATE-UNSECURED CONTROL SYSTEMS.
  
 2. WOULD YOU PLEASE SHOW ON A POOL PUMP CURVE AND
 IDENTIFY WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING
 INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM THE
 MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER THE
 ANSI/APSP/ICC 7 - 2015 SECS. 4.4.9, 4.4.9.1.
  
 3. THIS IS A MULTI-FAMILY DWELLINGS AND WATER USERS
 WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM. PLEASE PUT A NOT ON
 PLAN A SEPARATE PERMIT FOR BACKFLOW PER THE CITY OF
 WEST PALM BEACH CROSS CONNECTION PROGRAM AT THE
 UTILITITES DEPARTMENT.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved