| Date |
Text |
| 2021-10-05 11:23:05 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21090311 |
| | 10/5/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET F1: DESIGN CRITERIA- PLEASE PROVIDE A LIST OF |
| | CURRENT CODES AND STANDARDS USED IN THE DESIGN OF THE |
| | FOUNTAIN- SECTION 107.2.1 WPB. |
| | |
| | 2) F1: PLEASE PROVIDE A NOTE ON THE PLAN INDICATING |
| | THAT THE FOUNTAIN IS NOT FOR BATHING, SWIMMING, WADING |
| | OR FOR INTERACTIVE WATER ACTIVITIES- SECTION 454.1 FBC |
| | B. |
| | |
| | 3) F7.3: PLEASE CORRECT THE DETAIL SHOWING POOL WASTE |
| | BY GENERAL CONTRACTOR. THE ENGINEER OF RECORD SHALL |
| | DESIGN THE WASTE WATER REMOVAL SYSTEM IN ACCORDANCE |
| | WITH- SECTION 454.1.6.5.15 FBC B, AND SECS. 90-126 & |
| | 203 WPB CODE OF ORDINANCES. UNDER SEC. 90-126 (5) |
| | SWIMMING POOL DISCHARGES ARE PROHIBITED TO DRAIN INTO |
| | THE CITY SANITARY SYSTEM. UNDER SEC. 90-203 NO PERSON |
| | SHALL DIRECTLY OR INDIRECTLY DISCHARGE, SPILL, OR DUMP |
| | INTO ANY OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE |
| | STORM SEWER SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER |
| | THAN THAT COMPOSED OF STORMWATER. THERE IS AN EXCEPTION |
| | UNDER SEC. 90-205 FOR DECHLORINATED SWIMMING POOL |
| | DISCHARGES, HOWEVER THE ENGINEER MUST PROVIDE DETAILS |
| | AND SPECIFICATIONS FOR DECHLORINATION OF THE POOL WASTE |
| | WATER. |
| | |
| | 4) BASED ON COMMENT #2 ABOVE PLEASE PROVIDE A CIVIL |
| | PLAN OR SITE UTILITY PLAN SHOWING HOW WASTE WATER FROM |
| | THE POOL AND SPA WILL BE DRAINED TO AN APPROVED PLACE |
| | OF DISPOSAL- SECTION 107.2.1 WPB. |
| | |
| | 5) F7.3: PROVIDE TOTAL DYNAMIC HEAD CALCULATIONS TO |
| | VERIFY PUMP SIZING AND PUMP SELECTION SHOWN IN THE PUMP |
| | CURVE- SECTION 454.1.6.5.4 FBC B. THE CALCULATIONS |
| | SHALL INCLUDE THE CALCULATED HEAD FOR PIPING AND |
| | EQUIPMENT. |
| | |
| | 6) F7.3: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | RECIRCULATION AND TREATMENT EQUIPMENT INCLUDING THE |
| | PUMPS, FILTERS, CHLORINATOR AND MAIN DRAINS AND COVERS- |
| | SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |