| 2022-04-26 06:18:48 | 3RD REVIEW FMC |
| | PERMIT: 21090266 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ACCORDING TO FMC SECTION 403.3.1.1 AND TABLE |
| | 403.3.1.1 THE CALCULATIONS FOR VENTILATION FOR THIS |
| | BUILDING DO NOT MEET THE MINIMUM OUTDOOR AIR |
| | REQUIREMENTS. PLEASE READ THE 3RD SENTENCE OF SECTION |
| | 403.3.1.1 BELOW AS THIS SECTION TELLS US WE MUST USE |
| | TABLE 403.3.1.1 TO DETERMINE THE OCCUPANT COUNT FOR |
| | EACH SPACE AND NOT USE THE ARCHITECTS OCCUPANT COUNT. |
| | THE OUTDOOR AIR CALCULATIONS PRESENTED IN TIS CYCLE DO |
| | NOT SHOW ENOUGH OUTDOOR AIR BEING BROUGHT INTO THE |
| | SPACES. |
| | FMC 403.3.1.1 THE OCCUPANT LOAD UTILIZED FOR DESIGN OF |
| | THE VENTILATION SYSTEM SHALL BE NOT LESS THAN THE |
| | NUMBER DETERMINED FROM THE ESTIMATED MAXIMUM OCCUPANT |
| | LOAD RATE INDICATED IN TABLE 403.3.1.1. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |