Plan Review Notes
Plan Review Notes For Permit 21090266
Permit Number 21090266
Review Stop P
Sequence Number 2
Notes
Date Text
2022-01-11 13:27:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090266 4400 BEACON CIR
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 3. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOM INDICATING THE FOLLOWING:
 3E) SECOND REQUEST: PROVIDE DETAIL(S) FOR DRINKING
 FOUNTAIN(S) SHOWING COMPLIANCE WITH FBC ACC 602.4,
 602.5 AND 602.7.
 3E1)NEW REQUEST: SHOW CLEAR FLOOR SPACE FOR DRINKING
 FOUNTAIN WITH FORWARD APPROACH COMPLYING WITH FBC ACC
 602.2
 3E2).NEW REQUEST: SHOW KNEE AND TOE CLEARANCE FOR
 DRINKING FOUNTAIN COMPLYING WITH FBC ACC SECTION 306
  
 6. PARTIALLY COMPLIED-SEE COMMENT 6C BELOW.
 6C) SECOND REQUEST: PER WPB FBC 107.2.1 AND FBC PL
 421.5.2, SHOW LINER SLOPED AT 2 PERCENT SLOPE AND
 SPECIFY LINER MATERIAL; INDICATE BACKING, HEIGHT OF
 LINER ABOVE THRESHOLD, AND NAILING OF LINER. SEE BELOW.
 FBC PL 421.5.2 FLOORS UNDER SHOWER COMPARTMENTS, EXCEPT
 WHERE PREFABRICATED RECEPTORS HAVE BEEN PROVIDED, SHALL
 BE LINED AND MADE WATER-TIGHT UTILIZING MATERIAL
 COMPLYING WITH SECTIONS 421.5.2.1 THROUGH 421.5.2.6
 (SPECIFY LINER MATERIAL). SUCH LINERS SHALL TURN UP ON
 ALL SIDES NOT LESS THAN 2 INCHES (51 MM) ABOVE THE
 FINISHED THRESHOLD LEVEL. LINERS SHALL BE RECESSED AND
 FASTENED TO AN APPROVED BACKING SO AS NOT TO OCCUPY THE
 SPACE REQUIRED FOR WALL COVERING AND SHALL NOT BE
 NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH (25
 MM) ABOVE THE FINISHED THRESHOLD. LINERS SHALL BE
 PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED
 LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9.
  
 8. RE: P-2; KEYED PLUMBING NOTES;
 8A) SECOND REQUEST: PER WPB FBC 107.2.1, SHOW LOCATION
 OF KEY NOTE 1 ON THE FLOOR PLAN.
 8C1)NEW COMMENT REGARDING KEY NOTE 2 THE WATER SERVICE
 BACKFLOW PREVENTER AND THE SIZING:
 AMEND NOTE 2 TO INCLUDE "SEE CIVIL SHEET C-5 AND C-12
 FOR BACKFLOW PREVENTER LOCATION AND DETAIL"
  
 8B) COMPLIED
 8B1)SECOND REQUEST: PROVIDE SPECIFICATION AND DETAIL
 FOR CHILLER YARD BACKFLOW PREVENTER ON THE PLUMBING
 PLANS. TO BE CLEAR, THIS IS NOT PART OF THE CIVIL. IT
 NEEDS TO BE ON THE PLUMBING PLANS.
 8B2)NEW COMMENT: P-2; SHOW KEY NOTE 7 SYMBOL AT THE
 CHILLER YARD BACKFLOW PREVENTER.
 8B3)NEW COMMENT: P-9; SHOW WATER SUPPLY BRANCH AND
 BACKFLOW PREVENTER TO CHILLER YARD
  
 12. 12. PER WPB FBC 107.2.1, PROVIDE MANUFACTURERS
 SPECIFICATION AND A SCHEMATIC DETAIL FOR HEAT TRACE
 WIRING TO INCLUDE CONTROLS AND POWER SOURCE. COORDINATE
 WITH ELECTRICAL FOR POWER SOURCE.
 ENGINEER RESPONSE; SEE ELECTRICAL DRAWINGS FOR CONTROL
 AND POWER.
 PER WPB FBC 107.2.1, ADD TO P-2/KEY-NOTE 5 "SEE
 ELECTRICAL DRAWINGS FOR CONTROL AND POWER"
  
 14. PARTIALLY COMPLIED PER WPB FBC 107.2.1, PROVIDE
 CALCULATIONS FOR SIZING OF POTABLE WATER DISTRIBUTION.
 14A.NEW COMMENT: PLEASE ADVISE WHAT GPH STANDS FOR ON
 THE CHART. IS THIS SUPPOSED TO BE GPM?
 14B.NEW COMMENT: PER FBC PL APPENDIX E; TABLE E103.3(3)
 SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSHOMETER VALVES,
 DEMAND FOR 297 WSFU IS 108 GPM.
 FIGURE E103.3(3), FRICTION LOSS IN SMOOTH PIPEA (TYPE
 L, ASTM B88 COPPER TUBING) INDICATES 2? PIPE SUPPLYING
 100 GALLONS PER MINUTE IS GREATER THAN 10 FPS WITH A
 PRESSURE DROP OF APPROXIMATELY 7.5 PSI PER 100 FEET,
 WHICH IS NOT TAKING ANYTHING INTO ACCOUNT FOR FITTINGS,
 VALVES, ETC. THE CHART NOTES THAT VELOCITIES ABOVE 5 TO
 8 FPS ARE NOT USUALLY RECOMMENDED.
 PER WPB FBC 107.2.1, PLEASE REVISIT YOUR CALCULATIONS;
 SHOW DEMAND ON YOUR CHART AND RECONSIDER THE VELOCITY
 AND PIPE SIZES.
  
 23. SECOND REQUEST: P-10: PER FBC PL 914.2, THE CIRCUIT
 VENT CONNECTION SHALL BE LOCATED BETWEEN THE TWO MOST
 UPSTREAM (CIRCUIT VENTED) FIXTURE DRAINS ON THE MAIN
 BATTERY SERVICING THE MENS AND WOMENS TOILET ROOMS.
 FIRST FLOOR CIRCUIT VENT SHALL CONNECT BETWEEN THE
 MEN?S P-2 WATER CLOSET AND WOMEN?S P-1 WATER CLOSET,
 NOT UPSTREAM OF P-1.
 SECOND FLOOR CIRCUIT VENT SHALL CONNECT BETWEEN THE TWO
 WOMEN?S P-2 WATER CLOSETS, NOT UPSTREAM OF THEM.
  
 26.SECOND REQUEST: P-10: PER FBC PL 914.4, 914.4.1,
 PROVIDE A RELIEF VENT DOWNSTREAM OF THE CIRCUIT VENTED
 FIXTURES FOR EACH CIRCUIT VENTED BATTERY WITH FOUR OR
 MORE WATER CLOSETS.
 RELIEF VENT FOR SECOND FLOOR CIRCUIT VENT SHALL BE
 DOWNSTREAM OF P-1 WATER CLOSET, NOT BETWEEN P-1 AND
 P-2.
  
  
  
 NEW COMMENT: WHAT IS THE PURPOSE OF P-12/DETAIL 2
 SHOWER HEAD. IT DOES NOT SEEM TO APPLY TO ANY CONDITION
 IN THIS PROJECT. PER WPB FBC 107.2,1, PLEASE CLARIFY.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090266 4400 BEACON CIR
  