Plan Review Notes
Plan Review Notes For Permit 21090266
Permit Number 21090266
Review Stop M
Sequence Number 2
Notes
Date Text
2022-01-06 10:57:271ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21090266
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M10: PLEASE UNDERSTAND THAT YOU MUST CHOSE
 EITHER 2020 FBC M TABLE 403.3.1.1 OR ASHRAE 62.1-2016.
 THE DEMONSTRATION OF BLDG. VENTILATION TABLE HAS BOTH
 IN THE TITLE. PICK ONE AND USE IT TO PROVIDE THE
 OUTDOOR AIR CALCULATIONS. FBC M 403.3.1.1 STATES THAT
 YOU MUST USE TABLE 403.3.1.1 IN IT?S ENTIRETY NOT THE
 ARCHITECTURAL OCCUPANT COUNT. THE OUTDOOR AIR
 CALCULATIONS IS A 2 PART CALCULATION, THE SPACE BASED
 ON THE USE OF SPACE AND THE CFM?S FOR THE PEOPLE IN THE
 SPACE. PLEASE PROVIDE THE COMPLETE CALCULATION FOR EACH
 USE OF SPACE IN THIS BUILDING. IF YOU NEED ASSISTANCE
 WITH THIS PLEASE CONTACT ME.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  