Plan Review Notes
Plan Review Notes For Permit 21090266
Permit Number 21090266
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2021-12-29 13:54:09FIRE PROVISO:
  
 THERE ARE TWO(2) FDC'S INDICATED.
  
 INSTALL ONLY ONE (1) FDC FOR THE PROPOSED BUILDING AND
 INSTALL THE OTHER AT THE APPLICABLE TIME FOR ANY OTHER
 PROPOSED BUILDING.
  
 ALL FIRE LINE UNDERGROUND, INCLUDING THE DDCV & FDC,
 SHALL BE INSTALLED UNDER SEPARATE PERMIT & SHOP DRAWING
 AND PER NFPA 24
  
 PETER LEDUC
 FIRE MARSHAL