Plan Review Notes
Plan Review Notes For Permit 21090266
Permit Number 21090266
Review Stop B
Sequence Number 2
Notes
Date Text
2022-02-03 10:22:27PLAN
 REVIEW COMMENTS
 4400 BEACON CIRCLE
 2 STORY OFFICE BUILDING
 BUSINESS OCCUPANCY
 TYPE II-B CONSTRUCTION, SPRINKLERED
 FLOOD ZONE: X
 21,081 GROSS SQ-FT
 GROUND FLOOR ELEVATION: 16.0' NAVD88
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) RESOLVED.
  
 2) RESOLVED.
  
 3) [NOT RESOLVED.] SUBMIT A PLAN FOR SAFEGUARDS DURING
 CONSTRUCTION AND MOT. FBC CHAPTER 33
  
 4) RESOLVED.
  
 5) RESOLVED.
  
 6) RESOLVED.
  
 7) RESOLVED.
  
 8) RESOLVED.
  
 9) RESOLVED.
  
 10) RESOLVED.
  
 11) RESOLVED.
  
 12) [DEFERRED.] ON SHEET G003, THERE IS A HEADING
 "PROVISO DEFERRED SUBMITTAL". AMONG THE ITEMS THAT ARE
 LISTED FOR DEFERRED SUBMITTAL ARE PRODUCTS REGULATED BY
 DBPR RULE 9N-03, WHICH INCLUDES EXTERIOR DOORS,
 WINDOWS, STOREFRONTS, MULLIONS, WALL LOUVERS, ROOFING
 MATERIALS, ETC. IF YOU WISH TO DEFER THESE ITEMS IT IS
 NOT REQUIRED THAT YOU SUBMIT THEM PRIOR TO RECEIVING
 THE PERMIT. THEY DO HAVE TO BE SUBMITTED AND APPROVED
 BEFORE THEY ARE INSTALLED. FBC AMENDMENTS 107.3.4.1
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 13) [DEFERRED.] THE PRODUCT APPROVALS THAT WERE
 SUBMITTED HAVE NOT BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD FOR THIS PROJECT. FBC
 AMENDMENTS 107.3.4
  
 14) [DEFERRED.] THE PRODUCT APPROVALS FOR THE ROOFING
 AND PV RACKS ONLY HAVE THE COVERSHEETS. THE EVALUATION
 REPORT AND INSTALLATION INSTRUCTIONS WITH THE DESIGN
 PRESSURES ARE MISSING. THE SPECIFIC ROOF COVERING
 ASSEMBLIES AND THE DESIGN PRESSURES ARE REQUIRED TO BE
 CIRCLED OR HI-LITED IN THE PRODUCT APPROVAL. ENHANCED
 FASTENING CALCULATIONS MAY BE REQUIRED. FBC AMENDMENTS
 107.2.1
  
 15) [DEFERRED.] FOR ALL OF THE PRODUCT APPROVALS,
 SPECIFY ( HI-LITE OR CIRCLE) THE SPECIFIC ITEMS AND
 THEIR MAXIMUM DESIGN PRESSURES IN THE APPROVALS. FBC
 AMENDMENTS 107.2.1
  
 16) [DEFERRED.] SUBMIT PRODUCT APPROVALS OR SITE
 SPECIFIC ENGINEERING FOR THE PRE-FAB METAL CANOPY SHOWN
 IN DETAIL #3 ON SHEET A605. FBC AMENDMENTS 107.3.4
  
 17) THE VALUATION FOR THIS PROJECT HAS BEEN INCREASED
 FROM $3,800,000.00 TO $4,498,264.00 BASED ON THE
 CURRENT ICC VALUATION DATA. 21,081 SQFT X $213.38 =
 $4,498,263.78. FBC AMENDMENTS 109.3
  
 DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE LIST ON
 PLAN SHEET G003 (MAY NOT BE A COMPLETE LIST); DOCUMENTS
 SHOWING COMPLIANCE INCLUDING SHOP DAWINGS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL
 (ARCHITECT OR ENGINEER FOR PRODUCT APPROVALS AND OTHER
 SPECIFICATION DOCUMENTS, STRUCTURAL ENGINEER OF RECORD
 APPROVAL AND REVIEW IS REQUIRED FOR DELEGATED
 ENGINEERING). SUBMITTAL, REVIEW AND APPROVAL ARE
 REQUIRED PRIOR TO INSTALLATION.
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S010
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES.
  
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 BDA SYSTEMS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  