| 2021-11-02 14:23:15 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21090266 4400 BEACON CIR |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. ACCESSIBLE DETAILS ON A-900 ARE FOR A TRANSFER |
| | SHOWER COMPARTMENT. ID-1119 INDICATE AN ALTERNATE |
| | DESIGN ROLL-IN SHOWER. PER WPB FBC 107.2.1, PROVIDE |
| | ELEVATION VIEW OF SHOWER TO INCLUDE SIDE WALL. PROVIDE |
| | DIMENSIONS FOR LOCATIONS, ELEVATIONS OF SHOWER VALVE |
| | CONTROL ASSEMBLY, GRAB BARS. THRESHOLD; SHOW COMPLIANCE |
| | WITH FBC ACC 608.5.3, 608.3.3, 608.7 (NOTE, PER FBC ACC |
| | 608.7, THRESHOLDS IN ROLL-IN TYPE SHOWER COMPARTMENTS |
| | SHALL BE 1/2 INCH HIGH MAXIMUM IN ACCORDANCE WITH 303. |
| | IN TRANSFER TYPE SHOWER COMPARTMENTS, THRESHOLDS 1/2 |
| | INCH HIGH MAXIMUM SHALL BE BEVELED, ROUNDED, OR |
| | VERTICAL.) |
| | |
| | 2. PER WPB FBC 107.2.1, PROVIDE MINIMUM DIMENSION OF 36 |
| | INCHES FOR ROLL IN SHOWER ENTRY TO COMPLY WITH FBC ACC |
| | 608.2.3. |
| | |
| | 3. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | FOR NEW TOILET ROOM INDICATING THE FOLLOWING: |
| | ?A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 |
| | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC |
| | ACC 604.2 |
| | ?B) SHOW DIMENSIONS; CLEARANCE AROUND A WATER CLOSET |
| | SHALL BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| | THE SIDE WALL AND 56 INCHES MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL PER FBC ACC 604.3.1 |
| | ?C) PER FBC ACC 602.2, SHOW TOE AND KNEE CLEARANCE FOR |
| | ACCESSIBLE LAVATORIES AS REQUIRED BY FBC ACC 306.2 AND |
| | 306.3 |
| | ?D) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE (NOT THE BOTTOM OF THE UNIT) 40 |
| | INCHES (1015 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | ?E) PROVIDE DETAIL FOR DRINKING FOUNTAIN(S) SHOWING |
| | COMPLIANCE WITH FBC ACC 602.4, 602.5 AND 602.7 |
| | ?F) PLAN SHEET A101A, WOMENS SHOWER; MINIMUM ENTRY |
| | FINISH WIDTH SHALL BE 36 INCHES PER FBC ACC 608.2.3. |
| | ?G) SINK IN FIRST FLOOR BREAKROOM IS NOTED IN ELEVATION |
| | PLAN TO COMPLY WITH FBC ACC 606.3 FOR HEIGHT. SHOW |
| | CLEAR FLOOR SPACE FOR THE SINK IN ACCORDANCE WITH FBC |
| | ACC SECTION 305. IF A FORWARD APPROACH PROVIDE DETAIL |
| | SHOWING HOW KNEE AND TOE CLEARANCE IS PROVIDED AS |
| | REQUIRED BY FBC ACC 306.2 AND 306.3. |
| | ?H) IS THE SECOND FLOOR BREAKROOM SINK ACCESSIBLE? IF |
| | SO, SHOW CLEAR FLOOR SPACE COMPLYING WITH FBC ACC |
| | SECTION 305 AND PROVIDE DETAIL SHOWING COMPLIANCE WITH |
| | FBC ACC 606.3, 306.2 AND 306.3 AS REQUIRED. |
| | |
| | 4. MINIMUM FACILITIES; PER WPB FBC 107.2.1, PROVIDE A |
| | MINIMUM FACILITY PLUMBING SCHEDULE SHOWING COMPLIANCE |
| | WITH FBC PL TABLE 403.1; INDICATE MINIMUM FIXTURES |
| | REQUIRED FOR THE STATED OCCUPANCY AND OCCUPANT LOAD AND |
| | THE ACTUAL SUPPLIED. |
| | |
| | 5. PER WPB FBC 107.2.1, PROVIDE ELEVATION AND PLAN VIEW |
| | DRAWINGS FOR THE MENS TOILET ROOMS SIMILAR TO THAT |
| | SHOWN ON ID-1117 WOMENS TOILET ROOMS. |
| | |
| | 6. PER WPB FBC 107.2.1, PROVIDE A SHOWER WALL/DRAIN AND |
| | THRESHOLD DETAIL; NOTE, PER FBC ACC 608.7, THRESHOLDS |
| | IN ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 1/2 INCH |
| | HIGH MAXIMUM IN ACCORDANCE WITH 303. IN TRANSFER TYPE |
| | SHOWER COMPARTMENTS, THRESHOLDS 1/2 INCH HIGH MAXIMUM |
| | SHALL BE BEVELED, ROUNDED, OR VERTICAL. |
| | ?A) FBC PL 421.5.1 FLOORS OR RECEPTORS UNDER SHOWER |
| | COMPARTMENTS SHALL BE LAID ON, AND SUPPORTED BY, A |
| | SMOOTH AND STRUCTURALLY SOUND BASE. |
| | ?B) FBC PL 421.3 WASTE OUTLETS SERVING SHOWERS SHALL BE |
| | NOT LESS THAN 1-1/2 INCHES (38 MM) IN DIAMETER AND, FOR |
| | OTHER THAN WASTE OUTLETS IN BATHTUBS, SHALL HAVE |
| | REMOVABLE STRAINERS NOT LESS THAN 3 INCHES (76 MM) IN |
| | DIAMETER WITH STRAINER OPENINGS NOT LESS THAN 1/4 INCH |
| | (6.4 MM) IN LEAST DIMENSION. WHERE EACH SHOWER SPACE IS |
| | NOT PROVIDED WITH AN INDIVIDUAL WASTE OUTLET, THE WASTE |
| | OUTLET SHALL BE LOCATED, AND THE FLOOR PITCHED SO THAT |
| | WASTE FROM ONE SHOWER DOES NOT FLOW OVER THE FLOOR AREA |
| | SERVING ANOTHER SHOWER. WASTE OUTLETS SHALL BE FASTENED |
| | TO THE WASTE PIPE IN AN APPROVED MANNER. |
| | ?C) FBC PL 421.5.2 FLOORS UNDER SHOWER COMPARTMENTS, |
| | EXCEPT WHERE PREFABRICATED RECEPTORS HAVE BEEN |
| | PROVIDED, SHALL BE LINED AND MADE WATER-TIGHT UTILIZING |
| | MATERIAL COMPLYING WITH SECTIONS 421.5.2.1 THROUGH |
| | 421.5.2.6 (SPECIFY LINER MATERIAL). SUCH LINERS SHALL |
| | TURN UP ON ALL SIDES NOT LESS THAN 2 INCHES (51 MM) |
| | ABOVE THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE |
| | RECESSED AND FASTENED TO AN APPROVED BACKING SO AS NOT |
| | TO OCCUPY THE SPACE REQUIRED FOR WALL COVERING AND |
| | SHALL NOT BE NAILED OR PERFORATED AT ANY POINT LESS |
| | THAN 1 INCH (25 MM) ABOVE THE FINISHED THRESHOLD. |
| | LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 |
| | UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED |
| | TOWARD THE FIXTURE DRAINS AND BE SECURELY FASTENED TO |
| | THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A |
| | WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET. THE |
| | COMPLETED LINER SHALL BE TESTED IN ACCORDANCE WITH |
| | SECTION 312.9. |
| | |
| | 7. RE: P-1, PLUMBING GENERAL NOTES; |
| | ?A) NOTE 15, CALLS FOR PLUMBING PRECISION PRODUCT |
| | PR-500 TRAP PRIMER DEVICE. NOTE 37 CALLS FOR SIOUX |
| | CHIEF #695; DETAIL 6 ON P-11 CALLS FOR A FLUSHOMETER |
| | TAILPIECE TRAP PRIMER CONNECTION FOR TOILET ROOM FLOOR |
| | DRAINS AND ALL OTHER TO BE JOSAM 88250BB. PER WPB FBC |
| | 107.2.1, CLARIFY AND RECONCILE. PER WPB FBC 107.2.1, |
| | PROVIDE DETAIL FOR APPLICABLE DEVICE. |
| | ?B) NOTE 11 AND 16, RECONCILE THE TWO NOTES AND ADD |
| | ?ALL COMPONENTS IN POTABLE WATER SYSTEM TO BE LEAD FREE |
| | AS REQUIRED BY FBC PL 605.2, 6.5.2.1?. |
| | ?C) NOTE 43 SPECIFIES SANITARY FLOOR DRAINS FOR |
| | DIFFERENT APPLICATIONS. SANITARY DRAWINGS INDICATE ALL |
| | FLOOR DRAINS AS FD-1(INCLUDES JANITORS CLOSET FLOOR |
| | DRAIN, TOILET ROOM FLOOR DRAINS AND MECHANICAL ROOM |
| | FLOOR DRAINS WHICH ARE NOTED IN P-11/DETAIL 3 AS FLOOR |
| | SINKS FOR CONDENSATE) EXCEPT SHOWER DRAINS ARE FD-2. |
| | SOME LISTED IN 43 MAY NOT APPLY. IS THE FD-1 SHOWN IN |
| | THE FIRST FLOOR JANITORS CLOSET THE DRAIN FOR INDIRECT |
| | WASTE FROM THE WATER HEATER (PROVIDE NOTE IN WATER |
| | HEATER DETAIL)? THE NOTE CALLS FOR A 2 INCH FLOOR DRAIN |
| | W/FUNNEL? P10 RISER ONLY SHOWS A 3 INCH FLOOR DRAIN. |
| | ADDITIONALLY, DETAI8L 3/P11 SHOWS A FLOOR SINK. PER WPB |
| | FBC 107.2.1, CLARIFY. PROVIDE A DRAIN SCHEDULE FOR |
| | FLOOR DRAINS, ROOF DRAINS AND OVERFLOW ROOF DRAINS. TAG |
| | EACH ITEM AND RECONCILE SCHEDULE WITH SANITARY AND |
| | STORM DRAWINGS WITH EACH OTHER. |
| | |
| | 8. RE: P-2; KEYED PLUMBING NOTES; |
| | ?A) PER WPB FBC 107.2.1, SHOW LOCATION OF KEY NOTE 1 ON |
| | THE FLOOR PLAN. |
| | ?C) KEY NOTE 2 INDICATES BACKFLOW PREVENTER FOR |
| | BUILDING SERVICE. PER WPB FBC 107.2.1, PROVIDE |
| | MANUFACTURER, SPEC, MODEL AND INSTALLATION DETAIL. |
| | PLEASE NOTE, A SEPARATE PERMIT IS REQUIRED FOR THE |
| | BACKFLOW PREVENTER. |
| | ?B) SEE KEY NOTE 4. 3/4 INCH MAKE UP WATER TO CHILLER |
| | YARD REQUIRES A BACKFLOW PREVENTER PER FBC 608.3. PER |
| | WPB FBC 107.2.1, F.S.489 (I)(M) PROVIDE A LOCATION, |
| | SPECIFICATION AND DETAIL ON THE PLUMBING PLANS. ALL |
| | PIPE ROUTING DOWNSTREAM OF THE BACKFLOW PREVENTER SHALL |
| | BE SHOWN ON THE PLUMBING DRAWINGS F.S.489 (I)(M). |
| | |
| | 9. RE: P-3; KEYED PLUMBING NOTES; |
| | ?A) KEY NOTE 2 REFERENCES CIVIL DRAWINGS. PER WPB FBC |
| | 107.2.1, PROVIDE REQUIRED CIVIL DRAWINGS |
| | ?B) KEY NOTE 3 REFERENCES CIVIL DRAWINGS. PER WPB FBC |
| | 107.2.1, PROVIDE REQUIRED CIVIL DRAWINGS |
| | |
| | 10. PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE |
| | SCHEDULE/SPECIFICATION; TAG TO MATCH PLUMBING PIPING |
| | DRAWINGS. |
| | |
| | 11. WATER HEATER SCHEDULE & DETAIL- PER WPB FBC |
| | 107.2.1, PROVIDE THE FOLLOWING: |
| | ?A) WATER HEATER DETAIL 5/P-12; PER FBC PL 607.3, |
| | FURNISH A THERMAL EXPANSION CONTROL DEVICE BETWEEN THE |
| | CHECK VALVE AND THE WATER HEATER |
| | ?B) PROVIDE A WATER HEATER SCHEDULE LISTING |
| | MANUFACTURER, MODEL NUMBER, STORAGE CAPACITY, RECOVERY, |
| | ENERGY EFFICIENCY AND ELECTRICAL CHARACTERISTICS |
| | ?C) WATER HEATER DETAIL 5/P-12; PER WPB FBC 107.2.1, |
| | INDICATE T&P RELIEF VALVE COMPLYING WITH FBC PL 504.4 |
| | AND PROVIDE SIZE OF DISCHARGE PIPE COMPLYING WITH FBC |
| | PL 504.6. |
| | ?D) WATER HEATER DETAIL 5/P-12, PLAN SHEET P-2 AND P-9; |
| | PER WPB FBC 107.2.1, PROVIDE SIZE OF HOT AND COLD WATER |
| | INLET/OUTLET FOR THE WATER HEATER. |
| | ?E) WATER HEATER DETAIL 5/P-12; INDICATE ANTI SYPHON |
| | DEVICE I.E. COLD DIP TUBE OR FOR BOTTOM FED HEATER A |
| | VACUUM RELIEF VALVE PER FBC PL 504.1, 504.2 |
| | ?F) WATER HEATER DETAIL 5/P-12; INDICATE INTEGRAL HEAT |
| | TRAPS OR PROVIDE HEAT TRAPS IN HOT AND COLD WATER |
| | PIPING TO WATER HEATER PER FBC EC C404.3. |
| | |
| | 12. PER WPB FBC 107.2.1, PROVIDE MANUFACTURERS |
| | SPECIFICATION AND A SCHEMATIC DETAIL FOR HEAT TRACE |
| | WIRING TO INCLUDE CONTROLS AND POWER SOURCE. COORDINATE |
| | WITH ELECTRICAL FOR POWER SOURCE. |
| | |
| | 13. HANGER DETAIL- PER WPB FBC 107.2.1, AT PIPE HANGER |
| | DETAIL PROVIDE A NOTE STATING, "HORIZONTAL PIPE SHALL |
| | BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 14. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR |
| | SIZING OF POTABLE WATER DISTRIBUTION. |
| | |
| | 15. PER FBC PL 606.2, A SHUT OFF VALVE SHALL BE |
| | INSTALLED ON THE WATER SUPPLY PIPE TO EACH HOSE BIB, ON |
| | THE MAKEUP WATER TO THE ICE MAKER AND IN THE MAKEUP |
| | WATER TO THE CHILLER YARD. |
| | |
| | 16. FBC PL 419.5, PROVIDE TEMPERATURE LIMITING DEVICE |
| | TO DELIVER TEMPERED WATER TO LAVATORIES CONFORMING TO |
| | ASSE 1070 AND PROVIDE A DETAIL PER WPB FBC 107.2.1. |
| | |
| | 17. PER FBC PL 608.1, SPECIFY AND PROVIDE A BACKFLOW |
| | PREVENTER ON THE MAKEUP WATER TO THE ICE MAKER. |
| | |
| | 18. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR P-8 SINK |
| | AND ICEMAKER PIPING SHOWING PIPING ARRANGEMENT TO |
| | INCLUDE VALVES, BACKFLOW PREVENTER, ETC. |
| | |
| | 19. P-10: PER FBC PL 708.1.3, PROVIDE A CLEAN OUT AT OR |
| | NEAR THE JUNCTION OF THE BUILDING DRAIN AND BUILDING |
| | SEWER. |
| | |
| | 20. P-10: PER FBC PL 708.1.8, CLEAN OUT AT THE 90 |
| | DEGREE TURN OF THE BUILDING DRAIN SHALL BE INSTALLED TO |
| | ENABLE CLEANING ONLY IN THE DIRECTION OF FLOW. |
| | |
| | 21. P-10: PER WPB FBC 107.2.1, SHOW LOCATIONS OF |
| | CLEANOUTS INCLUDING AT BASE OF THE SOIL STACK AND |
| | UPSTREAM ENDS TO ALLOW CLEANING OF HORIZONTAL DRAINAGE |
| | PIPING (BUILDING DRAIN AND BRANCHES, FIRST AND SECOND |
| | FLOORS) ALLOWING CLEANING TO THE END OF THE BUILDING |
| | DRAIN. SHOW COMPLIANCE WITH FBC PL 708.1.1. |
| | |
| | 22. P-10: PER FBC PL 914.1.1, THE SOIL STACK SERVICING |
| | THE SECOND FLOOR SHALL DISCHARGE DOWNSTREAM OF THE |
| | VENTED TOILET ROOM BATTERY. |
| | |
| | 23. P-10: PER FBC PL 914.2, THE CIRCUIT VENT CONNECTION |
| | SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM (CIRCUIT |
| | VENTED) FIXTURE DRAINS ON THE MAIN BATTERY SERVICING |
| | THE MENS AND WOMENS TOILET ROOMS. |
| | |
| | 24. P-10: PER FBC PL 914.2 AND 914.1.1, ANOTHER CIRCUIT |
| | VENT CONNECTION SHALL BE LOCATED BETWEEN THE TWO WATER |
| | CLOSES SERVICING THE MENS AND WOMENS TOILET/SHOWER |
| | ROOMS. |
| | |
| | 25. BRANCH TO CIRCUIT VENTED WATER CLOSES SERVICING THE |
| | MENS AND WOMENS TOILET/SHOWER ROOMS IS UNDERSIZED. SIZE |
| | IN ACCORDANCE WITH FBC PL 914.3, 914.3.1 |
| | |
| | 26. P-10: PER FBC PL 914.4, 914.4.1, PROVIDE A RELIEF |
| | VENT DOWNSTREAM OF THE CIRCUIT VENTED FIXTURES FOR EACH |
| | CIRCUIT VENTED BATTERY WITH FOUR OR MORE WATER CLOSETS. |
| | |
| | 27. P-10: PER FBC PL 909.1, 909.2 AND 1002.3 (5), |
| | PROVIDE A VERTICAL VENT AT THE JUNCTION OF THE VERTICAL |
| | FIXTURE DRAIN AND THE HORIZONTAL PORTION CONNECTED TO |
| | THE URINAL. |
| | |
| | 28.P-10 SHOWS ALL WATER CLOSETS IN CIRCUIT VENTED |
| | BATTERY TO BE FLOOR MOUNTED. ID-117 WOMENS TOILET ROOM |
| | ELEVATION SHOWS WALL HUNG. PER WPB FBC 107.2.1, |
| | CLARIFY. |
| | |
| | 29. P-10; FIRST FLOOR: P-1 WATER CLOSET DOWNSTREAM OF |
| | P-8 SINK, FD-1 JANITORS CLOSET FLOOR DRAIN, FD-2 SHOWER |
| | AND P-11 MOP SINK SHALL BE INDIVIDUALLY VENTED IN |
| | ACCORDANCE WITH FBC PL 909.1 OR MAY BE COMMON VENTED IN |
| | ACCORDANCE WITH FBC PL 911, 911.2, 911.3 SECTIONS PER |
| | FBC PL 914.5. |
| | |
| | 30. P-10: PER FBC PL 909.1 AND 914.5, JANITORS CLOSETS |
| | FIRST AND SECOND FLOOR; PROVIDE VENTS FOR THE MOP SINKS |
| | AND FOR THE FLOOR DRAINS. |
| | |
| | 31. P10: SIZING IS SPOTTY. PER WPB FBC 107.2.1, PROVIDE |
| | SIZING BRANCHES AND FIXTURE DRAINS IN ACCORDANCE WITH |
| | FBC PL TABLES 709.1, 709.1(1), 709.1(2) AND 709.2. |
| | SIZING OF FIXTURE DRAINS MAY BE NOTED IN FIXTURE AND |
| | DRAIN SCHEDULES. BRANCHES SIZES SHALL BE NOTED AT EACH |
| | CHANGE IN SIZE AND AT CHANGES IN ELEVATION. |
| | |
| | 32. PER FBC 107.2.1, A RISER DIAGRAM FOR STORM WATER |
| | PIPING IS REQUIRED |
| | |
| | 33. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR |
| | SIZING OF STORM PIPING AND GUTTER SHOWING COMPLIANCE |
| | WITH FBC PL 1106.2, 1106.3 AND 1106.6. NOTE SLOPE OF |
| | HORIZONTAL PIPING ON THE PLANS. |
| | |
| | 34. GENERAL: WHEN REVISING PLANS IN RESPONSE TO THIS |
| | REVIEW, WHETHER IT BE RISER DIAGRAMS, PLAN VIEWS, |
| | SCHEDULES, NOTES OR DETAILS, PER WPB FBC 107.2.1, |
| | RECONCILE ALL PLANS WITH EACH OTHER. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21090266 4400 BEACON CIR |
| | |
| | |
| | |
| | |