| 2021-09-29 14:12:27 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21090266 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-2: THE WALLS SURROUNDING THE ELECTRICAL AND |
| | MECHANICAL ROOMS HAVE RATED WALLS ACCORDING TO LIFE |
| | SAFETY SHEET. PLEASE SHOW THE REQUIRED FIRE DAMPERS |
| | WHERE THE MECHANICAL DUCTS PENETRATE THESE RATED WALLS. |
| | FBC M 607 |
| | |
| | 2) SHEET M-2: PLEASE PROVIDE THE CFM'S OF SUPPLY AIR |
| | BEING DELIVERED TO THE ELECTRICAL ROOM. FBC 107.2.1 |
| | |
| | 3) SHEET M-9: EF-2 IS LOCATED ON THE 2ND FLOOR. IT IS |
| | EXHAUSTING 11 WATER CLOSETS/URINALS AND THE JANITOR'S |
| | CLOSET WHICH WOULD BE A TOTAL OF 600 CFM'S OF EXHAUST. |
| | PLEASE ADJUST THE EF-2 CFM'S TO A MINIMUM OF 600. FBC M |
| | TABLE 403.3.1.1 |
| | |
| | 4) SHEET M-9: PLEASE PROVIDE A DETAIL FOR EF-1 AND EF-2 |
| | TERMINATION ON THE ROOF. ARE THEY BOTH TERMINATING INTO |
| | THE EH-1? IF SO THE EH-1 CFM'S SHOULD BE ADJUSTED TO |
| | 1200 CFM'S AS IT APPEARS THE CFM'S SHOWN MAY HAVE |
| | OMITTED THE JANITOR'S CLOSET ON THE 2ND FLOOR. |
| | |
| | 5) SHEET M-10: OUTDOOR AIR CALCULATIONS: THE CURRENT |
| | FBC IS THE 2020 EDITION. THE FBC M REFERENCES THE |
| | ASHRAE 62.1-2016 EDITION, PLEASE REFERENCE THE CURRENT |
| | EDITION. IF YOU ARE USING ASHRAE FOR THE OUTDOOR AIR |
| | CALCULATIONS, PLEASE PROVIDE THE COMPLETE CALCULATIONS |
| | FOR EACH USE OF SPACE FOR THIS BUILDING SO THAT I CAN |
| | FOLLOW YOUR NUMBERS. FBC M 403.3.1.1 |
| | |
| | 6) SHEET M-10: VAV SCHEDULE: PLEASE CHECK THE MAX CFM'S |
| | FOR VAV 2-2 AS MY CALCULATIONS ARE 1535 CFM'S. FBC |
| | 107.2.1 |
| | |
| | 7) SHEET M-10: VAV SCHEDULE: PLEASE CHECK THE MAX CFM'S |
| | FOR VAV 2-4 AS MY CALCULATIONS ARE 1265 CFM'S. FBC |
| | 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |