2021-09-29 14:12:271ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21090266
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2: THE WALLS SURROUNDING THE ELECTRICAL AND
 MECHANICAL ROOMS HAVE RATED WALLS ACCORDING TO LIFE
 SAFETY SHEET. PLEASE SHOW THE REQUIRED FIRE DAMPERS
 WHERE THE MECHANICAL DUCTS PENETRATE THESE RATED WALLS.
 FBC M 607
  
 2) SHEET M-2: PLEASE PROVIDE THE CFM'S OF SUPPLY AIR
 BEING DELIVERED TO THE ELECTRICAL ROOM. FBC 107.2.1
  
 3) SHEET M-9: EF-2 IS LOCATED ON THE 2ND FLOOR. IT IS
 EXHAUSTING 11 WATER CLOSETS/URINALS AND THE JANITOR'S
 CLOSET WHICH WOULD BE A TOTAL OF 600 CFM'S OF EXHAUST.
 PLEASE ADJUST THE EF-2 CFM'S TO A MINIMUM OF 600. FBC M
 TABLE 403.3.1.1
  
 4) SHEET M-9: PLEASE PROVIDE A DETAIL FOR EF-1 AND EF-2
 TERMINATION ON THE ROOF. ARE THEY BOTH TERMINATING INTO
 THE EH-1? IF SO THE EH-1 CFM'S SHOULD BE ADJUSTED TO
 1200 CFM'S AS IT APPEARS THE CFM'S SHOWN MAY HAVE
 OMITTED THE JANITOR'S CLOSET ON THE 2ND FLOOR.
  
 5) SHEET M-10: OUTDOOR AIR CALCULATIONS: THE CURRENT
 FBC IS THE 2020 EDITION. THE FBC M REFERENCES THE
 ASHRAE 62.1-2016 EDITION, PLEASE REFERENCE THE CURRENT
 EDITION. IF YOU ARE USING ASHRAE FOR THE OUTDOOR AIR
 CALCULATIONS, PLEASE PROVIDE THE COMPLETE CALCULATIONS
 FOR EACH USE OF SPACE FOR THIS BUILDING SO THAT I CAN
 FOLLOW YOUR NUMBERS. FBC M 403.3.1.1
  
 6) SHEET M-10: VAV SCHEDULE: PLEASE CHECK THE MAX CFM'S
 FOR VAV 2-2 AS MY CALCULATIONS ARE 1535 CFM'S. FBC
 107.2.1
  
 7) SHEET M-10: VAV SCHEDULE: PLEASE CHECK THE MAX CFM'S
 FOR VAV 2-4 AS MY CALCULATIONS ARE 1265 CFM'S. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  