| 2021-10-20 13:18:36 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21090226 |
| | ADD: 5300 EAST AVENUE ROOMS 118, 119, 120 & 121. |
| | CONT: FISHER CONTRACTING |
| | TEL: 561-691-4716 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. OCT. 20TH/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE SHEET A-2 PROVIDES THE WIND DESIGN |
| | CRITERIA BUT NOT THE PRESSURES, PLEASE PROVIDE IN VASD. |
| | 2020 FBC-B 1603.1.4 WIND DESIGN DATA. DESIGN WIND |
| | PRESSURES TO BE USED FOR EXTERIOR COMPONENTS AND |
| | CLADDING MATERIALS SPECIFICALLY DESIGNED BY THE |
| | REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR THE |
| | DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 2) IN THE DOCUMENT FOLDER THERE IS A 48-PAGE DOCUMENT |
| | OF PRODUCT APPROVALS WINDOWS AND DOORS. THE SUB-SYSTEM |
| | IS IDENTIFIED BUT NOTHING ELSE. IDENTIFY GLAZING/ |
| | MULLIONS. PLEASE IDENTIFY IN THE PRODUCT APPROVAL |
| | BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE |
| | SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS |
| | WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & |
| | HEIGHT, SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE, |
| | LENGTH IF UNREINFORCED OR REINFORCED INFORMATION IF |
| | REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH |
| | OPENING SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. |
| | WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | APPROVED MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND |
| | SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| | SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| | USED IN THE TESTS. |
| | |
| | 3) SHEET A-5 REFERENCED BATHROOM DETAILS. THE SHEET IS |
| | MISSING ALL OF THE DETAILS FOR AN ACCESSIBLE SHOWER. |
| | SEE IN THE 2020 ACCESSIBILITY CODE SECTIONS 608, 609 & |
| | 610 PLEASE PROVIDE DETAILS FOR ACCESSIBILITY. |
| | |
| | 4) 2020 FBC-ACCESSIBILITY CODE SECTION 467.2.3.21.3. |
| | ALL SHOWERS IN BATHING ROOMS CONNECTED DIRECTLY TO THE |
| | RESIDENT ROOMS SHALL BE DESIGNED SO THAT A SHOWER CHAIR |
| | CAN BE EASILY ROLLED IN AND OUT OF THE SHOWER AREA. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE |
| | WORKING FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |