| 2021-09-21 14:28:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) LIFE SAFETY SHEETS - THERE IS AN INDICATION OF A |
| | SINGLE EXIT OFF OF THE 2ND & 3RD FLOORS. |
| | |
| | PER NFPA 101 CH 30, NEW APARTMENT BUILDINGS |
| | |
| | 30.2.4.6 A SINGLE EXIT SHALL BE PERMITTED IN BUILDINGS |
| | WHERE THE TOTAL |
| | NUMBER OF STORIES DOES NOT EXCEED FOUR, PROVIDED THAT |
| | ALL OF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) THERE ARE FOUR OR FEWER DWELLING UNITS PER STORY. |
| | (2) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 30.3.5. |
| | (3) THE EXIT STAIRWAY DOES NOT SERVE MORE THAN ONE-HALF |
| | STORY BELOW |
| | THE LEVEL OF EXIT DISCHARGE. |
| | (4) THE TRAVEL DISTANCE FROM THE ENTRANCE DOOR OF ANY |
| | DWELLING UNIT TO |
| | AN EXIT DOES NOT EXCEED 35 FT (10.7 M). |
| | (5) THE EXIT STAIRWAY IS COMPLETELY ENCLOSED OR |
| | SEPARATED FROM THE REST |
| | OF THE BUILDING BY BARRIERS HAVING A MINIMUM 1-HOUR |
| | FIRE RESISTANCE |
| | RATING. |
| | (6) ALL OPENINGS BETWEEN THE EXIT STAIRWAY ENCLOSURE |
| | AND THE BUILDING |
| | ARE PROTECTED WITH SELF-CLOSING DOOR ASSEMBLIES HAVING |
| | A MINIMUM |
| | 1-HOUR FIRE PROTECTION RATING. |
| | (7) ALL CORRIDORS SERVING AS ACCESS TO EXITS HAVE A |
| | MINIMUM 1-HOUR |
| | FIRE RESISTANCE RATING. |
| | (8) HORIZONTAL AND VERTICAL SEPARATION HAVING A MINIMUM |
| | 1?2-HOUR FIRE |
| | RESISTANCE RATING IS PROVIDED BETWEEN DWELLING UNITS. |
| | |
| | THE PROPOSED IS IN DIRECT VIOLATIONS OF (1), (4), (5) & |
| | (6) |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND DETAILED NARRATIVE. |
| | |
| | |
| | |
| | 2) COVER SHEET - THERE IS AN INDICATION OF A FIRE |
| | SPRINKLER SYSTEM. |
| | |
| | THERE ARE NO INDICATIONS OF FIRE SPRINKLER DOCUMENTS IN |
| | COMPLIANCE WITH F.A.C. 61G |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING |
| | DOCUMENTS. |
| | (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF |
| | PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR |
| | INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING |
| | PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S |
| | RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31, |
| | 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE AHJ. THE DOCUMENTS SHALL INCLUDE: |
| | (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS |
| | REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A |
| | RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND |
| | EXPERIENCE. |
| | (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY |
| | STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH |
| | THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS |
| | ARE INTENDED TO CONFORM TO. |
| | (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF |
| | RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF |
| | THE SYSTEM. |
| | (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT |
| | SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING |
| | DOCUMENTS. |
| | (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY |
| | FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE |
| | ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE |
| | STATED PURPOSE OF THESE RESPONSIBILITY RULES. |
| | (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND |
| | BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING |
| | DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR |
| | CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE |
| | OF SUCH DOCUMENTS. |
| | (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN |
| | ENGINEERING DOCUMENT ONLY FOR INFORMATION OR |
| | CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO |
| | ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER |
| | SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS |
| | RESPONSIBILITY. |
| | (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY |
| | DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST |
| | ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS. |
| | (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY |
| | ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN |
| | FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC |
| | AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND |
| | INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE |
| | REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES |
| | WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE |
| | AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A |
| | PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR |
| | AGENCY APPROVAL ACTION ON THE SAME PROJECT. |
| | SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW |
| | IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY?NEW |
| | 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08. |
| | |
| | ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE |
| | PERMIT & SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE THE REQUIRED DOCUMENTATION WITH THIS |
| | MASTER PERMIT. |
| | |
| | |
| | |
| | |
| | 2A) CIVIL SHEETS - THERE ARE NO INDICATIONS OF FIRE |
| | LINE, FDC AND FIRE DDCV DETAILS. |
| | |
| | PLEASE PROVIDE DETAILS FOR THE PROPOSED FIRE LINE, FDC |
| | AND DDCV LOCATIONS. |
| | |
| | ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED PER NFPA |
| | 24. PLEASE PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 3) 1ST FLOOR LIFE SAFETY SHEET - THERE IS AN INDICATION |
| | OF A COMMERCIAL SPACE WITH AN AREA OF 1,222 AND SQ FT |
| | OF 2,057 OCCUPANCY LOAD. |
| | |
| | PLEASE CLARIFY IS IS 1,222 OR 2,057 |
| | |
| | |
| | 3A) 1ST FLOOR LIFE SAFETY SHEET - THERE IS AN |
| | INDICATION OF 2 DOUBLE IN-SWING EXIT DOES TO THE |
| | COMMERCIAL SPACE. |
| | |
| | SHOULD THESE SPACES BE CONVERTED TO A MERCANTILE OR |
| | ASSEMBLY OCCUPANCY THESE DOORS ARE REQUIRED TO |
| | OUT-SWING. |
| | |
| | PLEASE REVIEW AND PROVIDE FOR CLARIFICATION OR CORRECT |
| | TO OUT-SWING FOR FLEX SPACE PURPOSES. |
| | |
| | |
| | |
| | 4) 1ST FLOOR LIFE SAFETY PLAN - THE SINGLE EXIT |
| | STAIRWAY EXITS INTO THE PARKING GARAGE. |
| | |
| | PER NFPA 101 CH 7, MEANS OF EGRESS. |
| | |
| | 7.2.3.5 DISCHARGE. |
| | 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE |
| | INTO A PUBLIC WAY, |
| | INTO A YARD OR COURT HAVING DIRECT ACCESS TO A PUBLIC |
| | WAY, OR INTO AN EXIT |
| | PASSAGEWAY. SUCH EXIT PASSAGEWAYS SHALL BE WITHOUT |
| | OPENINGS, OTHER |
| | THAN THE ENTRANCE TO THE SMOKEPROOF ENCLOSURE AND THE |
| | DOOR OPENING TO |
| | THE OUTSIDE YARD, COURT, OR PUBLIC WAY. THE EXIT |
| | PASSAGEWAY SHALL BE |
| | SEPARATED FROM THE REMAINDER OF THE BUILDING BY A |
| | 2-HOUR FIRE RESISTANCE |
| | RATING. |
| | 7.2.3.5.2 THE SMOKEPROOF ENCLOSURE SHALL BE PERMITTED |
| | TO DISCHARGE |
| | THROUGH INTERIOR BUILDING AREAS, PROVIDED THAT ALL OF |
| | THE FOLLOWING CRITERIA |
| | ARE MET: |
| | (1) THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.7. |
| | (2) THE DISCHARGE FROM THE SMOKEPROOF ENCLOSURE SHALL |
| | LEAD TO A FREE |
| | AND UNOBSTRUCTED WAY TO AN EXTERIOR EXIT, AND SUCH WAY |
| | SHALL BE |
| | READILY VISIBLE AND IDENTIFIABLE FROM THE POINT OF |
| | DISCHARGE FROM |
| | THE SMOKEPROOF ENCLOSURE. |
| | (3) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER AND |
| | CAPACITY OF |
| | EXITS COMPRISED OF SMOKEPROOF ENCLOSURES SHALL |
| | DISCHARGE THROUGH |
| | INTERIOR BUILDING AREAS IN ACCORDANCE WITH 7.7.2. |
| | |
| | THE STAIRWAY CANNOT EXIT INTO THE PARKING GARAGE. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 5) THERE IS NO INDICATIONS OF A REQUIRED FIRE ALARM. |
| | |
| | PER NFPA 101 CH. 30 |
| | |
| | 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 30.3.4.1 GENERAL. |
| | 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN |
| | HEIGHT OR WITH |
| | MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE MEETING |
| | THE REQUIREMENTS |
| | OF 30.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM |
| | SYSTEM IN ACCORDANCE |
| | WITH SECTION 9.6, EXCEPT AS MODIFIED BY 30.3.4.2 |
| | THROUGH 30.3.4.5. |
| | |
| | 61G15-32.008 DESIGN OF FIRE ALARMS, SIGNALING SYSTEMS |
| | AND CONTROL SYSTEMS. |
| | |
| | (1) FIRE ALARMS, SIGNALING, AND CONTROL SYSTEMS |
| | INCLUDE, BUT ARE NOT LIMITED TO, FIRE PROTECTION |
| | SUPERVISION AND ALARM CIRCUITS, ACTIVATION CONTROLS, |
| | AND REMOTE SIGNALING. |
| | (2) THE FIRE PROTECTION SYSTEM DESIGN SPECIFICATIONS |
| | SHALL BE BASED ON APPLICABLE NFPA STANDARDS, WHEN |
| | AVAILABLE, OR ALTERNATIVE ENGINEERING SOURCES AND GOOD |
| | ENGINEERING PRACTICE WHEN REQUIRED, AND SHALL COMPLY |
| | WITH THE PROVISIONS OF RULE 61G15-33.006, F.A.C. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2) FS. |
| | LAW IMPLEMENTED 471.033 FS. |
| | HISTORY--NEW 5-19-93, FORMERLY 21H-32.008. |
| | |
| | ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT |
| | & SHOP DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE. |
| | |
| | |
| | |
| | |
| | 6) EXIT SIGNAGE EMERGENCY LIGHTING - THERE DOES NOT |
| | APPEAR TO BE ANY CLEAR EXIT SIGNAGE THROUGHOUT THE |
| | PROPOSED OCCUPANCIES. |
| | |
| | 30.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL BE |
| | ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| | 30.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING IN |
| | ACCORDANCE WITH |
| | SECTION 7.9 SHALL BE PROVIDED IN ALL BUILDINGS FOUR OR |
| | MORE STORIES IN |
| | HEIGHT, OR WITH MORE THAN 12 DWELLING UNITS, UNLESS |
| | EVERY DWELLING UNIT |
| | HAS A DIRECT EXIT TO THE OUTSIDE OF THE BUILDING AT THE |
| | FINISHED GROUND LEVEL. |
| | 30.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL HAVE |
| | SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL BUILDINGS |
| | REQUIRING MORE |
| | THAN ONE EXIT. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT OR INDICATE WHERE THE EXIT |
| | SIGNS ARE LOCATED. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |