| 2021-10-26 16:42:50 | NEW 3 STORY BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE A LIFE SAFETY PLAN FOR THE 2ND FLOOR, |
| | 3RD FLOOR AND ROOF TERRACE - SHOW THE OCCUPANCY LOADS, |
| | EXIT ACCESS TRAVEL DISTANCE TO THE EXIT DISCHARGE ETC. |
| | FBC WPB 107.3.5.1.1 (6) |
| | |
| | 2) DRAWING LS-01 SHOWS BUILDING CONSTRUCTION TYPE (I) - |
| | PLEASE SHOW (IA OR IB) FBC CHAPTER 6 |
| | |
| | 3) DRAWING LS-01 DOES NOT SHOW THE OCCUPANCY FOR EACH |
| | ROOM - PLEASE SHOW THE OCCUPANT LOAD FOR EACH ROOM OR |
| | SPACE - FBC 1004.1.2 |
| | |
| | 4) 2 EXITS ARE REQUIRED FROM EACH STORY AND ROOF |
| | TERRACE FBC 1006.3 |
| | |
| | 5) THE TRASH CHUTE CANNOT OPEN TO A CORRIDOR - FBC |
| | 713.13.1 - FBC 713.13.3 CHUTE ACCESS ROOMS. |
| | ACCESS OPENINGS FOR WASTE OR LINEN CHUTES SHALL BE |
| | LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS |
| | THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| | IN ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO |
| | THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING |
| | PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS |
| | THAN 3/4 HOUR. DOORS SHALL BE SELF- OR |
| | AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN |
| | ACCORDANCE WITH SECTION 716.5.9.3. |
| | |
| | 6) PLEASE SHOW THE STAIR RISER HEIGHTS FBC 1011.5.2 |
| | |
| | 7) DRAWING A4-1.01 PLEASE SHOW THE BOTTOM HAND RAIL |
| | EXTENSION TO CONTINUE TO SLOPE (NOT LEVEL) - FBC 1014.6 |
| | |
| | 8) PLEASE PROVIDE THE EXTERIOR FRAMING DETAILS FBC WPB |
| | 107.2.1 |
| | |
| | 9) PLEASE PROVIDE THE EXTERIOR CLADDING (TEAK WOOD |
| | FINISH) DETAILS FBC WPB 107.2.1 |
| | |
| | 10) PLEASE SHOW THE HORIZONTAL ASSEMBLY HOURLY FIRE |
| | RATING TO COMPLY WITH FBC 711.2.4 |
| | |
| | 11) PLEASE SHOW THE ROOFING SYSTEM REQUIRED WIND DESIGN |
| | PRESSURES FBC 1603.1.4 |
| | |
| | 12) PLEASE SHOW THE GUARDRAIL HEIGHT FROM THE ROOF |
| | TERRACE FINISHED FLOOR TO THE TOP OF THE PARAPET (GUARD |
| | RAIL). FBC 1015.3 |
| | |
| | 13) PLEASE PROVIDE A SURVEY. |
| | |
| | 14) PLEASE SHOW THE COMMERCIAL RESTROOMS WALL FINISH - |
| | FBC 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 15) PLEASE PROVIDE COPIES OF ALL OF THE PRODUCT |
| | APPROVALS (NOA) MENTIONED ON THE DRAWINGS. |
| | |
| | 16) PROVIDED NOA 20-0813.03 FOR THE SLIDING WINDOWS |
| | REQUIRES SHUTTERS - PLEASE PROVIDE THE SHUTTER PRODUCT |
| | APPROVALS. PRODUCT APPROVALS THAT ARE NOT LISTED ON THE |
| | DRAWINGS NEED TO BE REVIEWED AND MARKED APPROVED BY THE |
| | DESIGNER OF RECORD FBC WPB 107.3.4 |
| | |
| | 17) DRAWING A1-1.01 SHOWS DOOR OR SOMETHING AS SF-2 - |
| | WHAT IS SF-2 ? |
| | |
| | 18) PLEASE SHOW THE COMMERCIAL RESTROOMS TO COMPLY WITH |
| | FBC ACCESSIBILITY - SHOW FIXTURE FLOOR SPACES, GRAB BAR |
| | LOCATION AND SIZE DIMENSIONS, TOILET PAPER HOLDER |
| | LOCATION DIMENSIONS, MIRROR LOCATION DIMENSIONS PER FBC |
| | ACCESSIBILITY CHAPTER 6. |
| | |
| | 19) PLEASE SHOW RESIDENTIAL UNIT COMPLIANCE WITH FHA - |
| | SHOW THE REQUIRED FLOOR SPACE IN THE UNITS - - |
| | REQUIREMENT 7 -USABLE KITCHENS AND BATHROOMS. |
| | SECTION 100.205(C)(3)(IV) REQUIRES THAT COVERED |
| | MULTIFAMILY DWELLINGS WITH A BUILDING ENTRANCE ON AN |
| | ACCESSIBLE ROUTE SHALL BE DESIGNED AND CONSTRUCTED IN |
| | SUCH A MANNER THAT ALL PREMISES WITHIN COVERED |
| | MULTIFAMILY DWELLING UNITS CONTAIN USABLE KITCHENS AND |
| | BATHROOMS SUCH THAT AN INDIVIDUAL IN A WHEELCHAIR CAN |
| | MANEUVER ABOUT THE SPACE. |
| | GUIDELINE(1)USABLE KITCHENS. USABLE KITCHENS WOULD MEET |
| | SECTION 100.205(C)(3)(IV) IF: |
| | (A)A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| | THAT ALLOWS A PARALLEL APPROACH BY A PERSON IN A |
| | WHEELCHAIR IS PROVIDED AT THE RANGE OR COOKTOP AND SINK |
| | AND EITHER A PARALLEL OR FORWARD APPROACH IS PROVIDED |
| | AT OVEN, DISH WASHER, REFRIGERATOR/FREEZER OR TRASH |
| | COMPACTOR. (SEE FIGURE FHAG-6) |
| | (B)CLEARANCE BETWEEN COUNTERS AND ALL OPPOSING BASE |
| | CABINETS, COUNTERTOPS, APPLIANCES OR WALLS IS AT LEAST |
| | 40 INCHES. |
| | (C)IN U-SHAPED KITCHENS WITH SINK OR RANGE OR COOKTOP |
| | AT THE BASE OF THE ?U?, A 60-INCH TURNING RADIUS IS |
| | PROVIDED TO ALLOW PARALLEL APPROACH, OR BASE CABINETS |
| | ARE REMOVABLE AT THAT LOCATION TO ALLOW KNEE SPACE FOR |
| | A FORWARD APPROACH. |
| | |
| | (2)USABLE BATHROOMS. TO MEET THE REQUIREMENTS OF |
| | SECTION 100.205(C)(3)(IV) EITHER. |
| | ALL BATHROOMS IN THE DWELLING UNIT COMPLY WITH OPTION |
| | 2, OR THE PROVISIONS OF PARAGRAPH (A): OR |
| | AT LEAST ONE BATHROOM IN THE DWELLING UNIT COMPLIES |
| | WITH THE PROVISIONS OF PARAGRAPH (B), AND ALL OTHER |
| | BATHROOMS AND POWDER ROOMS WITHIN THE DWELLING UNIT |
| | MUST BE ON AN ACCESSIBLE ROUTE WITH USABLE ENTRY DOORS |
| | IN ACCORDANCE WITH THE GUIDELINES FOR REQUIREMENTS 3 |
| | AND 4. |
| | |
| | 20) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| | CEILING DESCRIPTION) |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| | DROP CEILING DESCRIPTION) |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| | ATTACHED TO THE FLOORING) |
| | |
| | 21) PLEASE PROVIDE DETAILS SHOWING THAT THE UNIT |
| | SEPARATION WALLS COMPLY WITH THE AIRBORNE SOUND |
| | REQUIREMENTS FBC 1207.2 AIRBORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| | OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| | LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E90. ALTERNATIVELY, THE |
| | SOUND TRANSMISSION CLASS OF WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SHALL BE ESTABLISHED BY |
| | ENGINEERING ANALYSIS BASED ON A COMPARISON OF WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES HAVING SOUND |
| | TRANSMISSION CLASS RATINGS AS DETERMINED BY THE TEST |
| | PROCEDURES SET FORTH IN ASTM E90. PENETRATIONS OR |
| | OPENINGS IN CONSTRUCTION ASSEMBLIES FOR PIPING; |
| | ELECTRICAL DEVICES; RECESSED CABINETS; BATHTUBS; |
| | SOFFITS; OR HEATING, VENTILATING OR EXHAUST DUCTS SHALL |
| | BE SEALED, LINED, INSULATED OR OTHERWISE TREATED TO |
| | MAINTAIN THE REQUIRED RATINGS. THIS REQUIREMENT SHALL |
| | NOT APPLY TO ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL |
| | BE TIGHT FITTING TO THE FRAME AND SILL. |
| | |