2021-09-30 16:52:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. FBC R314.3, 315.1; FBC 107.2.1
  
 SPACE NEXT TO THE SINK LOOKS TO BE 12" OR MORE WHICH
 REQUIRES AN OUTLET. 210.52(C)(1)
 210.52(C)(1) WALL COUNTERTOP AND WORK SURFACE. A
 RECEPTACLE OUTLET
 SHALL BE INSTALLED AT EACH WALL COUNTERTOP AND WORK
 SURFACE THAT
 IS 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL
 BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 600
 MM
 (24 IN.) MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT
 SPACE
  