| 2022-02-17 11:19:32 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21090053 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THIS REVIEW IS FOR THE MAIN HOUSE ONLY. COTTAGE PERMIT |
| | NUMBER IS 22010888. THE CABANA WOULD BE CONSIDERED A |
| | HABITABLE SPACE AND MUST BE CONDITIONED. PLEASE SUBMIT |
| | MECHANICAL DRAWINGS FOR THIS CABANA. THE ELECTRICAL |
| | SHEET CALLS FOR A MINI SPLIT, IF THIS IS TO BE USED FOR |
| | THE CABANA PLEASE PROVIDE THE MECHANICAL EQUIPMENT |
| | SIZING CALCULATIONS ALONG WITH THE MECHANICAL DRAWING. |
| | |
| | 1) THE SQUARE FOOTAGE SUBMITTED FOR THE MAIN HOUSE IN |
| | THE ENERGY CALCULATIONS AND THE MECHANICAL EQUIPMENT |
| | SIZING CALCULATIONS DO NOT MATCH. PLEASE CORRECT THIS. |
| | |
| | 2) PLEASE PROVIDE DUCT SIZES ON DUCTS FROM AHU TO FIRST |
| | FLOOR AND DUCT FROM AHU TO TRANSFER BOX ABOVE THE |
| | MASTER BATH. FBC 107.2.1 |
| | |
| | 3) PLEASE PROVIDE A DETAIL OF THE ANCHORING OF THE |
| | CONDENSING UNIT. FBC RES M1307.2 |
| | |
| | 4) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZE AND |
| | TERMINATION LOCATION. FBC RES M1411.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |