| 2021-09-30 14:19:58 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21090053 |
| | 9/30/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET EP-1: BASED ON THE RISER DIAGRAM IT APPEARS |
| | THAT THE WATER CLOSET IN THE MASTER BATH IS NOT BEING |
| | VENTED PROPERLY. IF YOU ARE WET VENTING THE FIXTURE, |
| | THE DRAIN SHALL CONNECT HORIZONTALLY TO THE BRANCH |
| | DRAIN IN THE DIRECTION OF FLOW- SECTION P3108.1 FBC |
| | RES. |
| | |
| | 2) EP-1: IT APPEARS THE WASHING MACHINE ON THE 2ND |
| | FLOOR IS PART OF A STACKABLE WASHER/DRYER COMBO UNIT. |
| | PLEASE SHOW THE LOCATIONS OF THE SHUT OFF VALVES FOR |
| | THE WASHING MACHINE TO VERIFY THEY WILL IN AN |
| | ACCESSIBLE LOCATION- P2903.9.3 FBC RES. |
| | |
| | 3) EP-1: PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED |
| | FOR THE NEW GUEST COTTAGE- A COMPLETE REVIEW OF THE |
| | PLUMBING AT THE COTTAGE WILL NOT BE REVIEWED AT THIS |
| | TIME. PLEASE NOTE HOWEVER THAT THE CURRENT RISER |
| | DRAWING SHOWS A NON-COMPLIANT WET VENT FOR THE COTTAGE |
| | FIXTURE DRAINS- NOT MORE THAN ONE WET VENTED FIXTURE |
| | SHALL DISCHARGE UPSTREAM OF THE DRY VENTED FIXTURE |
| | DRAIN CONNECTION. |
| | |
| | 4) EP-1: IN ACCORDANCE WITH SECTION 7C OF THE WPB |
| | UTILITIES MANUAL FOR CROSS-CONNECTION CONTROL A |
| | BACKFLOW ASSEMBLY SHALL BE INSTALLED ON THE POTABLE |
| | WATER SERVICE TO THE MULTI- FAMILY PROPERTY. |
| | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |