| 2021-10-07 20:52:52 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. MINIMUM GEC SIZE FOR COLD WATER PIPE IS #4 CU NOT |
| | NUMBER #6. PROVIDE CORRECTION. NEC 250.66 |
| | |
| | 2. 100AMP PANEL FOR COTTAGE DOES NOT SHOW MAIN BREAKER. |
| | MAIN BREAKER REQUIRED FOR SEPARATE STRUCTURE BECAUSE |
| | THERE ARE MORE THAN 6 THROWS OF THE HAND. NEC 225.32 & |
| | 225.33 |
| | |
| | 3. SEPARATE PERMIT IS REQUIRED FOR COTTAGE STRUCTURE. |
| | FBC 105.1 |
| | |
| | 4. NOTE ON PLAN STATES AIC RATING WILL BE SUPPLIED BY |
| | FINAL INSPECTION. THIS IS NOT PERMITTED. AIC RATING |
| | WILL BE REQUIRED BEFORE PERMIT ISSUANCE. PROVIDE |
| | CORRECTION |
| | |
| | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | |
| | 5. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| | GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| | RE E3607.3 |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |