| Plan Review Notes For Permit 21090032 |
| Permit Number |
21090032 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-23 13:24:54 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = NEED TO | | | CHOOSE A ROOFING SYSTEM IN THE PRODUCT APPROVAL THAT | | | SHOWS THE REQUIRED WIND DESIGN PRESSURE PER FBC R TABLE | | | R301.2(2) - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED | | | IN THE PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE | | | ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR | | | ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A | | | HIGHER WIND PRESSURE THEN THE CHOSEN ROOFING SYSTEM - | | | SEE NOTES ON THE PRODUCT APPROVAL. | | | |
|