| 2021-09-03 08:21:49 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21081725 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE MORE INFORMATION ABOUT THE FIRE | | | DAMPERS IN THE CEILING OF THE 2 ROOMS. WHAT IS THE | | | RATING OF THESE ROOMS? ARE THERE FIRE DAMPERS WHERE THE | | | EXISTING DUCT PENETRATE THE RATED WALLS? IN THE SMALLER | | | ROOM, IS THERE NOT GOING TO BE A RETURN AIR GRILL? WHY | | | DO THE RETURN AIR GRILLS IN THESE ROOMS NOT HAVE A FIRE | | | DAMPER? | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|