| Plan Review Notes For Permit 21081619 |
| Permit Number |
21081619 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-22 07:34:35 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) SEPARATE PERMIT REQUIRED FOR CABANA | | | | | | 2) OUTLET SPACING IN CABANA TO MEET 210.52 | | | | | | 3) RISER DIAGRAM REQUIRED FOR CABANA. | | | | | | 4) NO ELECTRICAL WORK SHOWN ON MAIN HOUSE. |
|