| Plan Review Notes For Permit 21081557 |
| Permit Number |
21081557 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-12-14 13:28:19 | PROVIDE COMPLETE ROOFING INFORMATION FOR REVIEW: | | | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS). | | | A)FLAT ROOF ASSEMBLY. AND, CLEARLY MARK WHICH APPROVED | | | ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE | | | WITH THE DESIGN PRESSURES OF SEC. R301.1 | | | FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) PRODUCT APPROVAL AS REQUIRED | | | BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 |
|