2021-12-13 15:37:46NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21081557
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. PROVIDE OWNER'S NAME, BUILDER'S NAME, CORRECT
 PERMIT OFFICE IS WEST PALM BEACH NOT PALM BEACH COUNTY,
 CORRECT JURISDICTION IS 604700 NOT 601000.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)REVISE WALL TYPE ON ITEM 10(B) TO MATCH PLANS. PLANS
 DON'T SPECIFY WOOD FRAME WALL. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 D)CLARIFY DOOR INFORMATION ON PAGE 4. PLANS DON'T SHOW
 ANY WOOD DOOR ON THE EAST SIDE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC-. ENERGY CONSERVATION.
 NOTE: SEE EXTERIOR ELEVATIONS.
  
 F) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 2- OK.
 3-OK.
  
 4- DEFERRED SUBMITTAL: ROOF FRAMING PLAN AND STRUCTURAL
 DETAILS ON SHEET S-2 CALL FOR HAMBRO COMPOSITE FLOOR
 SYSTEM W/ 3" CONCRETE SLAB. PROVIDE COMPLETE SHOP
 DRAWINGS (SIGNED AND SEALED) SHOWING ALL FRAMING
 MEMBERS AND ALL STRUCTURAL CONNECTORS. NOTE: SUBMIT
 THESE SHOP DRAWINGS PRIOR TO CONSTRUCTION TO AVOID
 CONFLICTS/DELAYS.
 NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 5- OK
 6- OK
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ICF WALL SYSTEM SPECIFIED ON PLANS.
  
 B)FLAT ROOF ASSEMBLY. AND, CLEARLY MARK WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 C)WINDOW MULLION CLEARLY SPECIFY ALL MULLION SIZES TO
 BE USED.
 NOTE:CLEARLY IDENTIFY OPENING LOCATION TO AVOID
 DELAYS/CONFLICTS.
  
 D) ALL DOORS AND WINDOW TYPES SHOWN ON PLANS.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THOSE ALREADY SUBMITTED) AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 9- OK
  
 10- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ENGINEER IS
 SPECIFYING R-25 SPRAY FOAM INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE SPRAY FOAM INSULATION TO
 VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE THE
 REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER