2021-11-04 17:20:14NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21081557
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 2- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 3- DESIGN PRESSURES SPECIFIED ON THE WINDOW AND DOOR
 SCHEDULES ON SHEET A-2 DON'T CORRESPOND TO THE WIND
 DESIGN CRITERIA SPECIFIED ON COVER SHEET G-1. ENGINEER
 SPECIFIES ULTIMATE WIND SPEED OF 250MPH (194 MPH
 NOMINAL WIND SPEED). REVISE AS REQUIRED TO MATCH. SEC.
 R301.2.1 FBC-RESIDENTIAL.
  
 4- DEFERRED SUBMITTAL: ROOF FRAMING PLAN AND STRUCTURAL
 DETAILS ON SHEET S-2 CALL FOR HAMBRO COMPOSITE FLOOR
 SYSTEM W/ 3" CONCRETE SLAB. PROVIDE COMPLETE SHOP
 DRAWINGS (SIGNED AND SEALED) SHOWING ALL FRAMING
 MEMBERS AND ALL STRUCTURAL CONNECTORS. NOTE: SUBMIT
 THESE SHOP DRAWINGS PRIOR TO CONSTRUCTION TO AVOID
 CONFLICTS/DELAYS.
 NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 5- ROOF PLAN ON SHEET A-6. ROOF AREA ABOVE GARAGE NEEDS
 OVERFLOW SCUPPER AS REQUIRED BY SEC. R903.4.1
 FBC-RESIDENTIAL.
 NOTE: SECONDARY OVERFLOW SCUPPERS SHOWN ON THE MAIN
 ROOF NEED TO BE AT LEAST 2" ABOVE FINISH ROOF AS
 REQUIRED BY SEC. R903.4.1 FBC-RESIDENTIAL. PROVIDE
 DETAIL.
  
 6- DESIGNER OF RECORD TO SPECIFY THE EXTERIOR WALLS
 INSULATION R-VALUE AS REQUIRED BY SEC. R103.2
 FBC-ENERGY CONSERVATION.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ICF WALL SYSTEM SPECIFIED ON PLANS.
  
 B)FLAT ROOF ASSEMBLY. AND, CLEARLY MARK WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 C)WINDOW MULLION NOA 17-0630.01 SUBMITTED EXPIRED ON
 MAY 26, 2021. NEED CURRENT ONE AND SPECIFY ALL MULLION
 SIZES TO BE USED.
 NOTE:CLEARLY IDENTIFY OPENING LOCATION TO AVOID
 DELAYS/CONFLICTS.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THOSE ALREADY SUBMITTED) AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 9- PROVIDE COMPLETE STRUCTURAL BUCK DETAIL FOR OVERHEAD
 GARAGE DOOR ON ICF WALL AND ALL EXTERIOR DOORS AND
 WINDOWS. NOTE: CLEARLY SPECIFY BUCK SIZE AND FASTENER
 TYPE SIZE AND SPACING. SPECIFY MINIMUM EMBEDMENT INTO
 CONCRETE. SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 10- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ENGINEER IS
 SPECIFYING R-25 SPRAY FOAM INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE SPRAY FOAM INSULATION TO
 VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE THE
 REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 11- DRAWINGS S-1 AND S-2 ARE NOT SIGNED AND SEALED BY
 THE ENGINEER OF RECORD. DRAWINGS NEED TO HAVE THE
 ENGINEER'S ORIGINAL SEAL/SIGNATURE AS REQUIRED BY SEC.
 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,