| 2021-11-04 17:20:14 | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21081557 |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.5 FBC-ENERGY CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 2- LOT DRAINAGE |
| | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | R401.3 FBC-RESIDENTIAL. |
| | SEC. 107.2.5 CITY AMENDMENTS. |
| | SEC. 110.9 CITY AMENDMENTS. |
| | |
| | 3- DESIGN PRESSURES SPECIFIED ON THE WINDOW AND DOOR |
| | SCHEDULES ON SHEET A-2 DON'T CORRESPOND TO THE WIND |
| | DESIGN CRITERIA SPECIFIED ON COVER SHEET G-1. ENGINEER |
| | SPECIFIES ULTIMATE WIND SPEED OF 250MPH (194 MPH |
| | NOMINAL WIND SPEED). REVISE AS REQUIRED TO MATCH. SEC. |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 4- DEFERRED SUBMITTAL: ROOF FRAMING PLAN AND STRUCTURAL |
| | DETAILS ON SHEET S-2 CALL FOR HAMBRO COMPOSITE FLOOR |
| | SYSTEM W/ 3" CONCRETE SLAB. PROVIDE COMPLETE SHOP |
| | DRAWINGS (SIGNED AND SEALED) SHOWING ALL FRAMING |
| | MEMBERS AND ALL STRUCTURAL CONNECTORS. NOTE: SUBMIT |
| | THESE SHOP DRAWINGS PRIOR TO CONSTRUCTION TO AVOID |
| | CONFLICTS/DELAYS. |
| | NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE IN |
| | WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 5- ROOF PLAN ON SHEET A-6. ROOF AREA ABOVE GARAGE NEEDS |
| | OVERFLOW SCUPPER AS REQUIRED BY SEC. R903.4.1 |
| | FBC-RESIDENTIAL. |
| | NOTE: SECONDARY OVERFLOW SCUPPERS SHOWN ON THE MAIN |
| | ROOF NEED TO BE AT LEAST 2" ABOVE FINISH ROOF AS |
| | REQUIRED BY SEC. R903.4.1 FBC-RESIDENTIAL. PROVIDE |
| | DETAIL. |
| | |
| | 6- DESIGNER OF RECORD TO SPECIFY THE EXTERIOR WALLS |
| | INSULATION R-VALUE AS REQUIRED BY SEC. R103.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)ICF WALL SYSTEM SPECIFIED ON PLANS. |
| | |
| | B)FLAT ROOF ASSEMBLY. AND, CLEARLY MARK WHICH APPROVED |
| | ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE |
| | WITH THE DESIGN PRESSURES OF SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | C)WINDOW MULLION NOA 17-0630.01 SUBMITTED EXPIRED ON |
| | MAY 26, 2021. NEED CURRENT ONE AND SPECIFY ALL MULLION |
| | SIZES TO BE USED. |
| | NOTE:CLEARLY IDENTIFY OPENING LOCATION TO AVOID |
| | DELAYS/CONFLICTS. |
| | |
| | 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| | (INCLUDING THOSE ALREADY SUBMITTED) AS REQUIRED BY SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 9- PROVIDE COMPLETE STRUCTURAL BUCK DETAIL FOR OVERHEAD |
| | GARAGE DOOR ON ICF WALL AND ALL EXTERIOR DOORS AND |
| | WINDOWS. NOTE: CLEARLY SPECIFY BUCK SIZE AND FASTENER |
| | TYPE SIZE AND SPACING. SPECIFY MINIMUM EMBEDMENT INTO |
| | CONCRETE. SEC. R301.2.1 FBC-RESIDENTIAL. |
| | NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO |
| | THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 10- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ENGINEER IS |
| | SPECIFYING R-25 SPRAY FOAM INSULATION. PROVIDE ICC |
| | EVALUATION REPORT FOR THE SPRAY FOAM INSULATION TO |
| | VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. |
| | NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE THE |
| | REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 11- DRAWINGS S-1 AND S-2 ARE NOT SIGNED AND SEALED BY |
| | THE ENGINEER OF RECORD. DRAWINGS NEED TO HAVE THE |
| | ENGINEER'S ORIGINAL SEAL/SIGNATURE AS REQUIRED BY SEC. |
| | 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING |
| | PLANS/DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |