| 2021-10-16 11:05:54 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC R 301, INSTALLATION PROPOSED NOT CLEAR, REVISE | | | THE INSTALLATION SCHEDULE TO CLARIFY: | | | | | | THE ADDRESS ON THE SCHEDULE DOES NOT MATCH THE ADDRESS | | | ON THE APPLICATION | | | HORIZONTAL SPAN IS PROPOSED, ARE YOU INSTALLING THE | | | ACCORDIONS SO THEY OPEN UP AND DOWN? SPAN IS EQUAL TO | | | BLADE LENGTH | | | CONFIRM THAT THE DIMENSIONS PROVIDED ARE WIDTH X | | | HEIGHT, DUE TO PROPOSED INSTALLATION THIS IS NOT CLEAR | | | HOW HAVE YOU DETERMINED THAT THE SUBSTRATE IS CONCRETE? | | | IF MOUNTED ON THE SIDES, THIS IS TYPICALLY FILLED | | | CELLS. | | | | | | | | | 2. SEE PAGE 13, A FACTOR OF .9 REQUIRED FOR 3" EDGE | | | DISTANCE. 10" IS PROPOSED BUT STATES THAT IT HAS A | | | FACTOR OF .9. THE FACTOR IS REQUIRED BUT NOT APPLIED. | | | 10" X .9 = 9". THE SCHEDULE SHOULD PROPOSE 9". | | | | | | | | | |
|