| Date |
Text |
| 2021-10-12 12:50:53 | 10/12/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS A RECORD FOR SUITE |
| | 100 AS A DIFFERENT LOCATION, SO PLEASE ADDRESS THE AD |
| | STOP COMMENTS. |
| | |
| | 2. WOULD YOU PLEASE PROVIDE WHAT TYPE OF OCCUPANCY THIS |
| | INTERIOR BUILD-OUT WILL BE AND THE OCCUPANCY LOAD WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 3. WOULD YOU PLEASE GIVE THE LEVEL OF ALTERATION PER |
| | 2020 FLORIDA EXISTING BUILDING CODE 301.1. |
| | |
| | 4. WOULD YOU PLEASE PROVIDE THE MINIMUM NUMBER OF |
| | FIXTURES FOR THE OCCUPANT LOAD BASED ON THE ACTUAL USE |
| | OF THE BUILDING OR SPACE PER TABLE 403.1 MINIMUM NUMBER |
| | OF FIXTURES. |
| | |
| | 5. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE PIPPING |
| | THROUGH RATED WALLS OR THE FLOORS. PLEASE SUBMIT THE |
| | COMPLETE ASSEMBLY DETAILS FOR THE SYSTEMS PER THE WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | |
| | 6. ON SHEET P-1; |
| | |
| | A. UNDER GENERAL PLUMBING, NOTE NUMBER TWO REFERS TO |
| | THE 2017 BUILDING CODE. WOULD YOU PLEASE CORRECT TO THE |
| | CURRENT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. THERE IS VERBIAGE ABOUT TUB AND SHOWER VALVES THAT |
| | DO NOT DO WITH THIS PROJECT. |
| | |
| | C. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC WATER |
| | RISER DIAGRAM PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | D. THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER |
| | PIPING, FROM THE SOURCE OF HOT WATER TO THE FIXTURES, |
| | EXCEEDS 50 FEET. RECIRCULATING SYSTEM PIPING AND |
| | HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF |
| | HOT OR TEMPERED WATER. |
| | |
| | E. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES |
| | SHALL BE SUPPLIED TO THE SOURCE. THERE IS A TABLE THAT |
| | LIMITS THE SOURCE AND THE OUTLET; PLEASE REFER TO TABLE |
| | 405.5.1 FOR THE MAXIMUM ALLOWABLE PIPE LENGTH METHOD |
| | AND SIZE ACCORDANTLY. |
| | |
| | F. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM |
| | SHALL BE IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT |
| | IN THE FLORIDA ENERGY CODE SEC. C404.6.1. |
| | |
| | G. RECIRCULATING SYSTEM, THE PIPING SHALL BE INSULATED |
| | IN ITS ENTIRETY, INCLUDING THE SUPPLY AND RETURN PIPING |
| | OF A CIRCULATING PER C404.4 (A) INSULATION OF PIPING. |
| | |
| | I. WOULD YOU PLEASE SHOW LOCATIONS OF WATER HAMMER |
| | ARRESTORS PER THE 2020 FBC SEC. P604.9 |
| | |
| | 7. ON SHEET P-2; |
| | |
| | A. IT SHOWS A NEW SINK, AND IF ONE OF THEM IS A BREAK |
| | ROOM, PLEASE PROVIDE THE CLEAR FLOOR SPACE AND |
| | DIMENSION FOR CLEAR FLOOR SPACE OF 30? X 48? PER THE |
| | 2020 FBC SEC. ACC 305.3. |
| | |
| | B. PROVIDE CABINET DETAIL SHOWING THE SINK AND OR LAVS |
| | HEIGHT OF 34 INCHES MAXIMUM PER THE 2020 FBC ACC SEC. |
| | 606.3. |
| | |
| | C. IN THE OFFICES, ONE SINK NEEDS TO BE ACCESSIBLE. |
| | WOULD YOU PLEASE LABEL AND REFER TO LETTER C COMMENTS |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. IF PER THE FIXTURE TABLE A DRINKING FOUNTAIN IS |
| | REQUIRED OR ONE IS ON THAT FLOOR, SHOW HOW FAR AND THE |
| | ACCESSIBILITY DIMENSION OF IT PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | E. IS THERE AN ICE MAKER OR A COFFEE MAKER, AND IF SO, |
| | IT SHALL BE EQUIPPED WITH AN IN-LINE VACUUM BREAKER |
| | THAT COMPLIES WITH ASSE 1024 PER THE 2020 FBC SEC. |
| | 608.13.10. |
| | |
| | 8. WOULD YOU PLEASE SUBMIT A SLAB REPAIR DETAIL? SHOW |
| | THE WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE |
| | CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE. |
| | SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM |
| | EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING |
| | OF THE DOWELS IN THE CENTER. THE REPAIR SHALL ALSO |
| | INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED |
| | VAPOR BARRIER OVER THE SOIL. A COPY OF THE TERMITE |
| | CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |