| Plan Review Notes For Permit 21081431 |
| Permit Number |
21081431 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-25 17:00:55 | 1) PLEASE SHOW THE REQUIRED BATH EXHAUST FAN IN THE | | | MASTER SHOWER AREA. FBC RES M1507.4 | | | | | | 2) IS THERE TO BE A HOOD ABOVE THE RANGE? IF SO, WILL | | | IT BE DUCTED TO THE EXTERIOR? IF SO PLEASE SHOW THE | | | TERMINATION LOCATION. IF THERE IS A HOOD PLEASE PROVIDE | | | THE CFM'S OF THE EXHAUST AIR. FBC RES M1503 | | | | | | 3) SHEET M-1 PLEASE SHOW THE DRYER EXHAUST DUCT AND | | | TERMINATION LOCATION FOR ALL LOCATIONS OF W/D HOOK UPS. | | | FBC RES M1501 | | | | | | 4) PLEASE SHOW THE CONDENSATE PIPING AND TERMINATION | | | LOCATION FOR BOTH AHU'S. FBC RES M1411.3 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|