| 2021-10-03 08:41:31 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | BECAUSE IT APPEARS THAT THE APPLICANT BELIEVES THAT ONE |
| | OF THE SINGLE HUNG WINDOWS SHOULD HAVE DESIGN PRESSURES |
| | FOR OPENING 3 (AS WELL AS THE SLIDING GLASS DOOR), |
| | PROVIDE A FLOOR PLAN PREPARED BY THE ENGINEER WHICH |
| | TIES THE OPENINGS TO THE DESIGN PRESSURES SPECIFIED. |
| | |
| | FROM PREVIOUS LISTS, NO NEW DOCUMENTS UPLOADED FOR 3RD |
| | SUBMITTAL EXCEPT FOR A FLOOR PLAN WHICH STILL HAS TWO |
| | OPENINGS MARKED #3. |
| | |
| | SEE THE ENGINEERING; YOU HAVE WHAT THE ENGINEER REFERS |
| | TO AS "MARK 1-2, 4-5" AND ALSO "MARK 3". MARKS 1-2 AND |
| | 4-5 REQUIRE DESIGN PRESSURES OF +62.7/-62.7. SUBMIT A |
| | FLOOR PLAN PREPARED BY THE ENGINEER THAT CLEARLY SHOWS |
| | WHICH OPENINGS CORRELATE WITH THE DESIGN PRESSURES. |
| | |
| | THE FLOOR PLAN PREPARED BY THE CONTRACTOR HAS TWO |
| | OPENINGS LABELED AS #3, AND THE PRODUCT APPROVAL OPTION |
| | FOR -60/+80 MARKED ON PAGE 2 OF THE SINGLE HUNG PRODUCT |
| | APPROVAL. THIS IS THE 3RD REVIEW OF THE SAME DOCMENTS. |
| | |
| | REVISE THE SINGLE HUNG PRODUCT APPROVAL ON DRAWING PAGE |
| | 2 SO THAT YOU INDICATE THAT +80/-80 OPTION IS PROPOSED, |
| | OR HAVE THE ENGINEER REDUCE THE REQUIRED PRESSURES. THE |
| | PRODUCT APPROVAL PROPOSES THE STANDARD SILL, BUT THE |
| | STANDARD SILL HAS A LIMITATION OF -60/+80. THE HI-RISE |
| | FRAME SILL HAS A DESIGN PRESSURE LIMITATION OF -80/+80. |
| | |
| | |
| | |