| Date |
Text |
| 2021-09-07 10:57:42 | 09/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER |
| | DIAGRAM FOR WATER AND SANITARY PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING. |
| | |
| | 2. WOULD YOU PLEASE SHOW A CONTINUOUS LOOP FOR THE |
| | RECIRCULATING SYSTEM PER THE 2020 FBC SEC. ER 403.5.1.1 |
| | CIRCULATION SYSTEMS. |
| | |
| | 3. ON SHEET P 101 A; |
| | |
| | A. IT SHOWS A FLOOR DRAIN IN THE HOUSE AND THE GUEST |
| | HOUSE. THERE IS NO SOURCE OF WATER SHOWN TO THE TRAP |
| | PRIMER ON THE WATER DIAGRAM. WOULD YOU PLEASE CORRECT |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. ON THAT SAME PAGE, IT SHOWS A GD-1 IN GRARAGE AND |
| | P001 FOR THE PLUMBING SCHEDULE. THERE IS NO SUCH NOTE |
| | FOR IT. IF IT STANDS FOR GRAVITY DRAIN, WOULD YOU |
| | PLEASE PROVIDE DETAIL OR MANUFACTURES SPECIFICATION AND |
| | CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. THIS IS A MULTI-FAMILY DWELLING, AND WATER USERS |
| | WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION |
| | ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW |
| | ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF |
| | HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE |
| | BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER |
| | THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND |
| | THEIR CONNECTION CONTROL PROGRAM. A NOTE ON PLANS FOR A |
| | SEPARATE PERMIT FOR BACKFLOW WILL BE FINE. |
| | |
| | 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |