Plan Review Notes
Plan Review Notes For Permit 21081303
Permit Number 21081303
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-09-22 11:39:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF ACCESS GATE LOCATION(S)
 INCLUDING THE WIDTH OF EACH GATES.
  
 20' IS REQUIRED FOR FD ACCESS.
  
 PLEASE PROVIDE DETAILS.
  
  
 1A) THERE ARE NO INDICATIONS OF EXISTING FIRE HYDRANT
 LOCATIONS ALONG THE FENCE LINES.
  
 PLEASE PROVIDE FH LOCATIONS AND ENSURE THAT THE FENCE
 IS NOT OBSTRUCTING THOSE FH'S.
  
  
  
 2) KNOX PADLOCKS ARE RECOMMENDED/NOT REQUIRED, AT EACH
 GATE LOCATION TO ENSURE FD ACCESS WITHOUT COMPROMISING
 SITE SECURITY.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  