| Plan Review Notes For Permit 21081303 |
| Permit Number |
21081303 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-22 11:39:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE NO INDICATIONS OF ACCESS GATE LOCATION(S) | | | INCLUDING THE WIDTH OF EACH GATES. | | | | | | 20' IS REQUIRED FOR FD ACCESS. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 1A) THERE ARE NO INDICATIONS OF EXISTING FIRE HYDRANT | | | LOCATIONS ALONG THE FENCE LINES. | | | | | | PLEASE PROVIDE FH LOCATIONS AND ENSURE THAT THE FENCE | | | IS NOT OBSTRUCTING THOSE FH'S. | | | | | | | | | | | | 2) KNOX PADLOCKS ARE RECOMMENDED/NOT REQUIRED, AT EACH | | | GATE LOCATION TO ENSURE FD ACCESS WITHOUT COMPROMISING | | | SITE SECURITY. | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|