| 2021-09-07 10:19:47 | COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST. |
| | PLEASE COMPLY. |
| | |
| | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21081294 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- FLAT ROOF NOA 18-0919.07 SUBMITTED: SELECTED |
| | ASSEMBLIES FOR THE INSULATED AND NON-INSULATED ROOF |
| | SYSTEMS DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF |
| | ZONES. PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS |
| | FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS |
| | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA. |
| | NEED THE CALCULATIONS TO MEET THE DESIGN PRESSURES |
| | REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. |
| | NOTE: THIS BUILDING IS LOCATED IN EXPOSURE "D". |
| | |
| | 2- ROOFING UNDERLAYMENT |
| | PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE |
| | NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. |
| | SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| | NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| | FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE |
| | PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001 |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |